Troubleshooting
172
Electrical Control System
2.4.2.9
High temperature protection of condenser(ODU P5)
When outdoor pipe temperature is more than 65°C, the unit will stop, and unit runs again when outdoor
pipe temp. less than 52°C.
High temperature protection of
condenser
Check whether the
condenser temperature is
more than 65°C
Yes
Judge 1: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Judge 3: The refrigerant
pipe is blocked
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 2: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Replace outdoor main board
Yes
Check whether the
resistance of condenser
temp. sensor is correct
refer to the
Appendix
1
Replace the temperature sensor
Stop the unit
Yes
No
No