Electrical Control System
2.4.2.5 High pressure protection (ODU P1) (For AWAU-YCZ430-H11, AWAU-YCZ536-H11)
High pressure protection
Judge 1: Whether the wiring
between the high pressure
switch and main control
board is connected well or
correctly
Method: Short connect the
high pressure protector
socket, check whether the
system can run normally
Yes
No
Connect it well
Replace outdoor main board
No
Replace high pressure protector
Yes
Judge 2: Whether
the high pressure
protector is broken
Check whether
the refrigerant
system is ok
Judge 3: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Stop the unit
Yes
Judge 4: Check whether the
outdoor unit is bad
ventilation
No
Make the outdoor unit ventilate well
Yes
Judge 5: Check whether the
heat exchanger is dirty
Clean the heat exchanger
Yes
Judge 6: Check whether the
refrigerant pipe is blocked
Let the refrigerant out, then use the
high pressure nitrogen or refrigerant to
blow pipe, vacuumize and charge the
refrigerant again
Yes