For Cassette & Duct:
When the compressor is on, the indoor fan can be set to high, medium, low and auto. And the anti-cold wind
function has the priority.
Auto fan action:
-3.5
T1-Ts-
Δ
T
-4
High
Low
-5
Medium
-4.5
1.3.3.4 Prevent Over-Heating
In heating mode, when the indoor unit has no capacity requirement due to indoor room temperature
increased, the Indoor fan will run in super breeze. (Anti-cold wind function has the priority)
1.3.3.5 Defrosting mode
:
Condition of defrosting:
If any one of the following items is satisfied, AC will enter the defrosting mode.
After the compressor starts up and keeps running, mark the minimum value of T3 from the 10th minutes to
15th minutes as T30.
1)If the compressor cumulate running time is up to 29 minutes and T3< TCDI1, T3
+
T30SUBT3ONE
≦
T30.
2)If the compressor cumulate running time is up to 35 minutes and T3< TCDI2, T3
+
T30SUBT3TWO
≦
T30.
3)If the compressor cumulate running time is up to 29 minutes and T3< TCDI3 for 3 minutes.
4)If the compressor cumulate running time is up to 120 minutes and T3<-15
℃
.
Condition of ending defrosting:
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to normal
heating mode.
Summary of Contents for AWAU-YCZ218-H11
Page 24: ...Dimensions Outdoor Units 97 AWAU YCZ536 H11...
Page 29: ...Wiring Diagrams 102 Outdoor Units AWAU YCZ327 H11 7SP091167 AWAU YCZ327 H11 7SP091171...
Page 30: ...Wiring Diagrams Outdoor Units 103 AWAU YCZ430 H11 7SP091168 AWAU YCZ430 H11 7SP091172...
Page 31: ...Wiring Diagrams 104 Outdoor Units AWAU YCZ536 H11 7SP091169 AWAU YCZ542 H11 7SP091173...
Page 107: ...SERVICE MANUAL Multi Splits Series...