Npaq® Hardware Manual
Maintenance
4.9. Preventative Maintenance
The Npaq and external wiring should be inspected monthly. Inspections may be required at more frequent
intervals, depending on the environment and use of the system. The table below lists the recommended
checks that should be made during these inspections.
D A N G E R : Disconnect power to the Npaq main supply before servicing.
Table 4-16:
Preventative Maintenance
Check
Action to be Taken
Visually Check chassis for loose or damaged parts
/ hardware.
Note
: Internal inspection is not required.
Parts should be repaired as required. If internal
damage is suspected, these parts should be
checked and repairs made if necessary.
Inspect cooling vents.
Remove any accumulated material from vents.
Check for fluids or electrically conductive material
exposure.
Any fluids or electrically conductive material must
not be permitted to enter the Npaq.
Visually inspect all cables and connections.
Tighten or re-secure any loose connections.
Replace worn or frayed cables. Replace broken
connectors.
Cleaning
The Npaq chassis can be wiped with a clean, dry, soft cloth. The cloth may be slightly moistened if required
with water or isopropyl alcohol to aid in cleaning if necessary. In this case, be careful not to allow moisture to
enter the Npaq or onto exposed connectors / components. Fluids and sprays are not recommended because
of the chance for internal contamination, which may result in electrical shorts and/or corrosion. The electrical
power must be disconnected from the Npaq while cleaning. Do not allow cleaning substances or other fluids
to enter the Npaq or to get on to any of the connectors. Avoid cleaning labels to prevent removing the label
information.
118
Chapter 4
www.aerotech.com