ADAM-4000 Series User Manual
182
4080
7.2.4.2
@AAGN
Name
Read Initial Count Value of Counter 0 or 1 command
Description
Read the initial count value of counter 0 or 1 of the
specified counter module at address AA.
Syntax
@AAGN(data)(cr)
@
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
GN
is the Read Initial Count Value for Counter 0 or 1 command.
N = 0 represents counter 0
N = 1 represents counter 1
(cr)
is the terminating character, carriage return (0Dh).
Response !AA(data)(cr)
if the command is valid.
There is no response if the module detects a syntax or
communication error, or even if the specified address does not exist.
!
is a delimiter character which indicates a valid command.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the module.
(data)
is the initial count value which must consist of eight
hexadecimal digits.
(cr)
is the terminating character, carriage return (0Dh).
Example
command: @12G0(cr)
response: !12000000FF(cr)
The command instructs the module at address 12h to return
the initial value of counter 0. The module replies that
initial count value of counter 0 is 000000FF.
Summary of Contents for Adam - 4021
Page 1: ...User Manual ADAM 4000 Series Data Acquisition Modules...
Page 4: ...ADAM 4000 Series User Manual iv...
Page 12: ...ADAM 4000 Series User Manual xii...
Page 13: ...Chapter 1 1 Introduction...
Page 16: ...ADAM 4000 Series User Manual 4...
Page 17: ...Chapter 2 2 Installation Guideline...
Page 33: ...Chapter 3 3 I O Modules...
Page 78: ...ADAM 4000 Series User Manual 66...
Page 79: ...Chapter 4 4 Command Set...
Page 99: ...87 ADAM 4000 Series User Manual Chapter 4 Command Set...
Page 100: ...ADAM 4000 Series User Manual 88...
Page 101: ...Chapter 5 5 Analog Input Module Commands...
Page 127: ...Chapter 6 6 Analog Output Module Commands...
Page 144: ...ADAM 4000 Series User Manual 132...
Page 145: ...Chapter 7 7 I O Relay Counter Frequency...
Page 201: ...Chapter 8 8 Calibration...
Page 206: ...ADAM 4000 Series User Manual 194...
Page 207: ...Appendix A A Technical Specifications...
Page 216: ...ADAM 4000 Series User Manual 204 Figure A 5 ADAM 4024 Function Diagram...
Page 232: ...ADAM 4000 Series User Manual 220 Figure A 14 ADAM 4080 Function Diagram...
Page 233: ...Appendix B B Data Formats and I O Ranges...
Page 244: ...ADAM 4000 Series User Manual 232...
Page 245: ...Appendix C C Technical Diagrams...
Page 246: ...ADAM 4000 Series User Manual 234 C 1 ADAM Dimensions Figure C 1 ADAM Modules Dimensions...
Page 248: ...ADAM 4000 Series User Manual 236 Figure C 3 DIN Rail Mounting...
Page 250: ...ADAM 4000 Series User Manual 238 C 2 3 Piggyback Stack Figure C 6 Piggyback Stack...
Page 251: ...Appendix D D Utility Software...
Page 258: ...ADAM 4000 Series User Manual 246...
Page 259: ...Appendix E E RS 485 Network...
Page 264: ...ADAM 4000 Series User Manual 252...
Page 265: ...Appendix F F Using the Checksum Feature...
Page 268: ...ADAM 4000 Series User Manual 256...
Page 269: ...Appendix G G I O Modbus Mapping Table...
Page 283: ...Appendix H H Changing to Modbus Protocol...
Page 285: ...273 ADAM 4000 Series User Manual Appendix H Changing to Modbus Protocol...