7.2
Counter/Frequency Module Command
7.2.1
Configuration, Counter Input and Display Command Set
4080
7.2.1.1
%AANNTTCCFF
Name
Configuration command
Description
Sets the address, input mode, baud rate, checksum status
and frequency gate time for a specified counter/frequency module
Syntax
%AANNTTCCFF (cr)
%
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address that you will access to.
NN
represents the new hexadecimal address of the
counter/frequency module. Range is from 00h to FFh.
TT
represents the input mode.
50h : counter input mode
51h : frequency measurement mode
CC
represents the baud rate code.
(Refer to Table 7-3 on next page).
Hexadecimal value FF which is converted to an 8-bit
parameter represents the checksum status and frequency
gate time. The layout of the 8-bit parameter is shown in
Figure 7-3 below.
Bits 0, 1, 3, 4, 5 and 7 are not used and are set to 0.
(cr)
is the terminating character, carriage return (0Dh).
Command Syntax Description
I/O Module
%AANNTTCCFF
Sets the address, input mode, baud rate, checksum
status and/or frequency gate time for a specified
counter/frequency module
4080
$AA2
Requests the return of the configuration data from the
counter/frequency module
4080
$AAF
Requests the counter/frequency module to return the
version code of its firmware
4080
$AAM
Requests the counter/frequency module to return its
name
4080
$AABS
Set the input signal mode of the specified
counter/frequency module to either non-isolated
(TTL) or photo-isolated.
4080
$AAB
Read the input mode of the specified
counter/frequency module.
4080
#AAN
Instructs the addressed counter/ frequency module to
read the counter or frequency value of counter 0 or
counter 1 and return the acquired data.
4080
Summary of Contents for Adam - 4021
Page 1: ...User Manual ADAM 4000 Series Data Acquisition Modules...
Page 4: ...ADAM 4000 Series User Manual iv...
Page 12: ...ADAM 4000 Series User Manual xii...
Page 13: ...Chapter 1 1 Introduction...
Page 16: ...ADAM 4000 Series User Manual 4...
Page 17: ...Chapter 2 2 Installation Guideline...
Page 33: ...Chapter 3 3 I O Modules...
Page 78: ...ADAM 4000 Series User Manual 66...
Page 79: ...Chapter 4 4 Command Set...
Page 99: ...87 ADAM 4000 Series User Manual Chapter 4 Command Set...
Page 100: ...ADAM 4000 Series User Manual 88...
Page 101: ...Chapter 5 5 Analog Input Module Commands...
Page 127: ...Chapter 6 6 Analog Output Module Commands...
Page 144: ...ADAM 4000 Series User Manual 132...
Page 145: ...Chapter 7 7 I O Relay Counter Frequency...
Page 201: ...Chapter 8 8 Calibration...
Page 206: ...ADAM 4000 Series User Manual 194...
Page 207: ...Appendix A A Technical Specifications...
Page 216: ...ADAM 4000 Series User Manual 204 Figure A 5 ADAM 4024 Function Diagram...
Page 232: ...ADAM 4000 Series User Manual 220 Figure A 14 ADAM 4080 Function Diagram...
Page 233: ...Appendix B B Data Formats and I O Ranges...
Page 244: ...ADAM 4000 Series User Manual 232...
Page 245: ...Appendix C C Technical Diagrams...
Page 246: ...ADAM 4000 Series User Manual 234 C 1 ADAM Dimensions Figure C 1 ADAM Modules Dimensions...
Page 248: ...ADAM 4000 Series User Manual 236 Figure C 3 DIN Rail Mounting...
Page 250: ...ADAM 4000 Series User Manual 238 C 2 3 Piggyback Stack Figure C 6 Piggyback Stack...
Page 251: ...Appendix D D Utility Software...
Page 258: ...ADAM 4000 Series User Manual 246...
Page 259: ...Appendix E E RS 485 Network...
Page 264: ...ADAM 4000 Series User Manual 252...
Page 265: ...Appendix F F Using the Checksum Feature...
Page 268: ...ADAM 4000 Series User Manual 256...
Page 269: ...Appendix G G I O Modbus Mapping Table...
Page 283: ...Appendix H H Changing to Modbus Protocol...
Page 285: ...273 ADAM 4000 Series User Manual Appendix H Changing to Modbus Protocol...