ADAM-4000 Series User Manual
92
Response
!AA(cr)
if the command is valid.
?AA(cr)
if an invalid parameter was entered or if the INIT*
terminal was not grounded when attempting to change baud
rate or checksum settings.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
! delimiter character indicates a valid command was received.
? delimiter character indicates the command was invalid
AA
(range 00-FF) represents the 2-character hexadecimal
address of an analog input module.
(cr)
is the terminating character, carriage return (0Dh)
Example
command:%2324050600(cr)
response:!24(cr)
The ADAM-4011 module with address 23h is configured to
a new address of 24h, an input range ±2.5 V, baud rate
9600, integration time 50 ms (60 Hz), engineering units
data format and no checksum checking or generation.
The response indicates that the command was received.
Wait 7 seconds to let the new configuration settings take
effect before issuing a new command to the module.
Caution!
Only ADAM-4018+ support “% of FSR” and “two’s complement of hexa
-
decimal” Data Format.
Caution!
An analog input module requires a maximum of 7 seconds to perform
auto calibration and ranging after it is reconfigured.
During this time span, the module cannot be addressed to perform any
other actions.
Caution!
All configuration parameters can be changed dynamically, except
checksum and baud rate parameters. They can only be altered when
the INIT* terminal is grounded. (Refer to Baud rate and Checksum con
-
figuration in Chapter 2, for the correct procedure)
Table 5.1: Input Range Codes (Type Codes)
Input Range Code (Hex)
Input Range for 4018+ (Thermocouple and ± 20 mA only)
00
± 15 mV
01
± 50 mV
02
± 100 mV
03
± 500 mV
04
± 1 V
05
± 2.5 V
06
± 20 mA
07
4~20mA
Summary of Contents for Adam - 4021
Page 1: ...User Manual ADAM 4000 Series Data Acquisition Modules...
Page 4: ...ADAM 4000 Series User Manual iv...
Page 12: ...ADAM 4000 Series User Manual xii...
Page 13: ...Chapter 1 1 Introduction...
Page 16: ...ADAM 4000 Series User Manual 4...
Page 17: ...Chapter 2 2 Installation Guideline...
Page 33: ...Chapter 3 3 I O Modules...
Page 78: ...ADAM 4000 Series User Manual 66...
Page 79: ...Chapter 4 4 Command Set...
Page 99: ...87 ADAM 4000 Series User Manual Chapter 4 Command Set...
Page 100: ...ADAM 4000 Series User Manual 88...
Page 101: ...Chapter 5 5 Analog Input Module Commands...
Page 127: ...Chapter 6 6 Analog Output Module Commands...
Page 144: ...ADAM 4000 Series User Manual 132...
Page 145: ...Chapter 7 7 I O Relay Counter Frequency...
Page 201: ...Chapter 8 8 Calibration...
Page 206: ...ADAM 4000 Series User Manual 194...
Page 207: ...Appendix A A Technical Specifications...
Page 216: ...ADAM 4000 Series User Manual 204 Figure A 5 ADAM 4024 Function Diagram...
Page 232: ...ADAM 4000 Series User Manual 220 Figure A 14 ADAM 4080 Function Diagram...
Page 233: ...Appendix B B Data Formats and I O Ranges...
Page 244: ...ADAM 4000 Series User Manual 232...
Page 245: ...Appendix C C Technical Diagrams...
Page 246: ...ADAM 4000 Series User Manual 234 C 1 ADAM Dimensions Figure C 1 ADAM Modules Dimensions...
Page 248: ...ADAM 4000 Series User Manual 236 Figure C 3 DIN Rail Mounting...
Page 250: ...ADAM 4000 Series User Manual 238 C 2 3 Piggyback Stack Figure C 6 Piggyback Stack...
Page 251: ...Appendix D D Utility Software...
Page 258: ...ADAM 4000 Series User Manual 246...
Page 259: ...Appendix E E RS 485 Network...
Page 264: ...ADAM 4000 Series User Manual 252...
Page 265: ...Appendix F F Using the Checksum Feature...
Page 268: ...ADAM 4000 Series User Manual 256...
Page 269: ...Appendix G G I O Modbus Mapping Table...
Page 283: ...Appendix H H Changing to Modbus Protocol...
Page 285: ...273 ADAM 4000 Series User Manual Appendix H Changing to Modbus Protocol...