ADAM-4000 Series User Manual
110
4015, 4017+, 4018+, 4019+
5.1.18
$AA7CiRrr
Name
Single Channel Range Configuration command
Description
This command configures the input type and range of the
specified channel in an analog input module.
Syntax
$AA7CiRrr(cr)
$
is a delimiter character.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the analog input module which is to be configured.
7
is the Single Channel Range Configuration command.
Ci
represents the specified input channel you want to configure.
Rrr
represents the type and range you want to set. (Refer to
Table 5.1 on Page 5-6 to check range codes)
(cr)
is the terminating character, carriage return (0Dh).
Response
!AA(cr)
if the command was valid.
?AA(cr)
if an invalid operation was entered.
There is no response if the module detects a syntax error or
communication error or if the specified address does not exist.
!
delimiter character indicates a valid command was received.
?
delimiter character indicates the command was invalid.
AA
(range 00-FF) represents the 2-character hexadecimal
address of the analog input module.
(cr)
represents terminating character, carriage return (0Dh).
Example
command: $027C5R21(cr)
response: !02(cr)
The command configures the range of channel 5 in the
analog input module at address 02 as Pt100(IEC) 0 ~ 100 °C
Summary of Contents for Adam - 4021
Page 1: ...User Manual ADAM 4000 Series Data Acquisition Modules...
Page 4: ...ADAM 4000 Series User Manual iv...
Page 12: ...ADAM 4000 Series User Manual xii...
Page 13: ...Chapter 1 1 Introduction...
Page 16: ...ADAM 4000 Series User Manual 4...
Page 17: ...Chapter 2 2 Installation Guideline...
Page 33: ...Chapter 3 3 I O Modules...
Page 78: ...ADAM 4000 Series User Manual 66...
Page 79: ...Chapter 4 4 Command Set...
Page 99: ...87 ADAM 4000 Series User Manual Chapter 4 Command Set...
Page 100: ...ADAM 4000 Series User Manual 88...
Page 101: ...Chapter 5 5 Analog Input Module Commands...
Page 127: ...Chapter 6 6 Analog Output Module Commands...
Page 144: ...ADAM 4000 Series User Manual 132...
Page 145: ...Chapter 7 7 I O Relay Counter Frequency...
Page 201: ...Chapter 8 8 Calibration...
Page 206: ...ADAM 4000 Series User Manual 194...
Page 207: ...Appendix A A Technical Specifications...
Page 216: ...ADAM 4000 Series User Manual 204 Figure A 5 ADAM 4024 Function Diagram...
Page 232: ...ADAM 4000 Series User Manual 220 Figure A 14 ADAM 4080 Function Diagram...
Page 233: ...Appendix B B Data Formats and I O Ranges...
Page 244: ...ADAM 4000 Series User Manual 232...
Page 245: ...Appendix C C Technical Diagrams...
Page 246: ...ADAM 4000 Series User Manual 234 C 1 ADAM Dimensions Figure C 1 ADAM Modules Dimensions...
Page 248: ...ADAM 4000 Series User Manual 236 Figure C 3 DIN Rail Mounting...
Page 250: ...ADAM 4000 Series User Manual 238 C 2 3 Piggyback Stack Figure C 6 Piggyback Stack...
Page 251: ...Appendix D D Utility Software...
Page 258: ...ADAM 4000 Series User Manual 246...
Page 259: ...Appendix E E RS 485 Network...
Page 264: ...ADAM 4000 Series User Manual 252...
Page 265: ...Appendix F F Using the Checksum Feature...
Page 268: ...ADAM 4000 Series User Manual 256...
Page 269: ...Appendix G G I O Modbus Mapping Table...
Page 283: ...Appendix H H Changing to Modbus Protocol...
Page 285: ...273 ADAM 4000 Series User Manual Appendix H Changing to Modbus Protocol...