www.advancedco.com
90
7.8 USER Menu Functions
The following table gives a list of the USER Menu Functions, the sub-functions available within each main function
and a brief description for each function.
Main Menu Option
Sub Menus
Comments
VIEW
Alarms
View Zones and Inputs that are reporting an alarm condition.
Off-Normal
View Zones, Inputs and Outputs that are reporting an off-normal condition.
(Alarms, Supervisory, Trouble, Disabled, Pre-Alarm, Warning, Problems and
MNS-Alarm)
Network
View Network diagnostics
Inputs
View the current state of Inputs (by zone/point).
Outputs
View the current operational condition of all Output circuits (by zone/point).
Log
View the Event Log and Alarm Counter
Panel
View Local-Hardware, Software and Network-Hardware. Local-Hardware - view
operational state, voltage and current loading of the panel input and output
circuits. Software – view software revisions for Panel, Display, SLC, Network,
PSU and Peripherals. Network-Hardware – view network node voltage and
current loading of the network node panel input and output circuits.
DISABLE
Zone / Inputs
35
Disable a complete zone or an individual input device.
Outputs
35
Disable NAC outputs or other output devices.
Groups
35
Group Disable – Disable a programmed group of inputs / outputs
Controls
36
Cancel Level 2 panel access.
User ID
35
Return Level 2 access to the default User 1
ENABLE
Zone / Inputs
35
Enable a complete zone or an individual input device.
Outputs
35
Enable NAC outputs or other output devices.
Groups
35
Group Enable – Re-enable a group of inputs / outputs
Remote
35
Grant remote access for terminal mode or ipGateway
TEST Zones
35
Configure one or more zones for walk test.
Display
Test the Display, Status Indicators (including Switch LED Module LEDs) and
Keyboard.
Buzzer
Test the Internal Buzzer
Printer
Test the connection to the Printer
Outputs
Test Outputs in the system
Audio
35
Test Audio area amplifier (s) with massage type (1 – 16 messages within
amplifier [s])
P.A.S
Enabled
Enable P.A.S. operation
Disabled
Disable P.A.S. operation
TOOLS
Program
Enter the Level 3 Commissioning and Panel Programming Functions
(factory default Level 3 programming code 7654)
Setup printer and print inputs, outputs, troubles, disabled, log
Change Time
Change time and date of the system
STATUS
---
Return to the Normal Operating Display immediately
35
This option can be configured per User ID. User 1 does not have permission to change these options.
36
Not required if a key switch is fitted to change access levels.