![Advanced Axis AX-CTL-1L Installation & Operation Manual Download Page 83](http://html1.mh-extra.com/html/advanced/axis-ax-ctl-1l/axis-ax-ctl-1l_installation-and-operation-manual_2855749083.webp)
www.advancedco.com
83
Example of an unacknowledged supervisory event, when no alarms or mass notification events are present (refer to
Fire Alarm Condition, for displaying supervisory events with alarms or mass notification events present on the
system):
NEW SUPERVISORY ZONE 0020
< New supervisory message (unacknowledged)
Electrical Room
Sprinkler System Riser [SWITCH(MON.)]
< Zone supervisory text (32 Characters)
< Device text (26 Characters) / type of device
(Press
→
for device details)
.
WRNs: 0 SUPRVs: 1 DISBLs: 0 TRBLs: 0
.
< Further device details
< # Warnings, Supervisory, Disables and
Troubles
Example of an unacknowledged trouble event:
NEW TROUBLE ZONE 0010
< New trouble message (unacknowledged)
First Floor West Wing
Conference Room [PHOTO SMOKE ]
< Zone trouble text (32 Characters)
< Device text (26 Characters) / type of device
DEVICE MISSING
(Press
→
for device details)
.
WRNs: 0 SUPRVs: 0 DISBLs: 0 TRBLs: 1
.
< Type of Trouble
< Further device details
< # Warnings, Supervisory, Disables and
Troubles
Example of multiple unacknowledged events:
NEW SUPERVISORY ZONE 0020 (Scroll
↓
)
< New supervisory message, w/scroll active
Electrical Room
Sprinkler System Riser [SWITCH(MON.)]
< Zone supervisory text (32 Characters)
< Device text (26 Characters) / type of device
(Press
→
for device details)
.
WRNs: 0 SUPRVs: 1 DISBLs: 0 TRBLs: 2
.
< Further device details
< # Warnings, Supervisory, Disables and
Troubles
During unacknowledged, non-alarm and non-MNS events, the display only indicates the highest priority event and a
tally of any additional events. The additional events may be viewed by scrolling (Scroll
↓
) through the display. The
scroll (Scroll
↓
) feature is only active when multiple unacknowledged viewable events are present.
Pressing the “ACK” button will acknowledge the event condition(s). This changes the event LED (pre-alarm,
supervisory, disable, system trouble) to steady, the internal buzzer will silence, and the display will show “Off-
Normal State: Total”. Off-normal state totals are listed in order of system priority; Pre-Alarms, Warnings,
Supervisory, Troubles and Disabled. Off-normal state totals are only displayed if an active event within that priority
is present on the system.
Note: The AX-CTL-1L, AX-CTL-2 and AX-CTL-4 intelligent fire alarm control panel acknowledges on a
“Global” basis; all events are acknowledged with the single activation of the acknowledge button.
Example of acknowledged non-alarm events (no pre-alarm events present on the system):
[Off-Normal State : Total] (Scroll
↓
)
< Off-Normal line, w/scroll
(
Scroll shown only with multiple events)
WARNINGS : 1
SUPERVISORY : 1
TROUBLES : 2
DISABLED : 4
< Off-Normal type and event total
Only active off-normal events are displayed
(i.e.: Pre-Alarms not displayed)
(Press
✔
to select)
< More info pertaining to highlighted event