Switch Monitor Module - 55000-805ADV
The 55000-805ADV Switch Monitor Module is designed to mount to the front of a 4” square or 2- gang electrical box.
Based on installation requirements, the Switch Monitor Module’s initiating device circuit (IDC) is capable of being
wired Class A or B to the monitored contact device(s). An integral eight position programming DIP switch provides
programming of device address and wiring classification definition. Each 55000-805ADV Switch Monitor Module
incorporates a red status LED which flashes when the device is polled. Switch Monitors can monitor any number of
contact devices, however it is recommended not to mix alarm, supervisory, or security contacts on the same
monitoring module circuit (see figure 10).
Priority Switch Monitor Module - 55000-806ADV
The 55000-806ADV Priority Switch Monitor Module is identical to the 55000-805ADV, Switch Monitor Module, with the
exception of a priority interrupt feature. The priority interrupt provides the fastest response possible to the AX-CTL-
1L, AX-CTL-2 or AX-CTL-4 AX-CTL base card. When the priority interrupt device is in an active state, the monitor’s
priority interrupt bypasses the normal SLC communications process, and immediately allows the device to
communicate with the AX-CTL-1L, AX-CTL-2 or AX-CTL-4 AX-CTL base card. The Priority Switch Monitor Module
is utilized to monitor highly critical contact devices such as manual pull stations (see Figure 10).
L2
+
-
+
-
To Next
Peripheral
From
SLC Loop
Class A Wiring
A/B+
A/B-
A+
A-
L1
TB5
TB1
1234
5678
1
2
4
8
16
32
64
NO
B
A
1
0
Programming
DIP Switches
E
O
L
Class B Wiring
47K
1/2 Watt
A/B+
A/B-
A+
A-
SW1
TB3
Figure 10 - 55000-805ADV and 55000-806ADV Wiring