AX-NET4: Class B AD-NeT-PluS network:
32 Network Nodes (requires 150
Ω
filtering resistor at the beginning
and at the end of the network)
Maximum Cable Length 5000ft
AX-NET7: Class X (Class A, Style 7) AD-NeT-PluS network:
200
Network
Nodes
Maximum Cable Length between Nodes 5000ft
Maximum Overall Cable Length 66000ft
Cable wiring must be minimum twisted shielded pair 18AWG to 20AWG.
Connect the shield to the designated terminal block positions only.
Refer to Axis
AX
Wiring Guide Section 9.
Note: Optional AX-MOXA Fiber Optic Converter Modules are available for
converting AX-NET4 or AX-NET7 copper wiring to fiber optic.
4.8.1 Installing the AX-NET4 or AX-NET7 Module
Note: All Axis
AX
fire alarm control panels can support networking capabilities.
The AX-NET4 and AX-NET7 modules are supplied with one metal hexagon spacer/screw and three (3) nylon
spacers (see figure 30).Install the metal hexagon spacer [h] and three (3) supplied nylon spacers [n]. Plug the flat
ribbon cable of the AX-NET4/AX-NET7 into the dedicated network connector on the AX-CTL base card. Position the
module onto the three (3) nylon spacers and snap in place. Secure the module in place by screwing the supplied
screw [p] into the metal hexagon spacer (see figure 30). It is critical that this screw is tightly secured as the screw is
required for the earth ground connection to the AX-NET4/AX-NET7 module.
A
OUT
B
OUT
SCN
A
IN
B
IN
SCN
Shield
A
B
A
Shield
B
To Base Card
Figure 30 - AX-NET4 or AX-NET7 Installation