www.advancedco.com
69
Note: Two (2) AX-RL4 modules can be mounted in an AXM-009 enclosure.
4.17 AX-CZM Conventional Zone Module
The AX-CZM is an Advanced conventional zone module that can be monitored and controlled by an Axis
AX
fire
alarm control panel (see figure 43). The AX-CZM conventional zone module provides monitoring for up to eight (8)
Class B conventional zones, with programmable end-of-line, or four (4) Class A conventional zones. In addition,
each AX-CZM module has three (3) field programmable Form C relay contacts defaulted to activate on common
alarm. Up to sixteen (16) AX-CZM modules can be supported by a single Axis
AX
fire alarm control panel. By
supporting sixteen (16) AX-CZM modules, an Axis
AX
fire alarm control panel can accommodate up to 128 Class B
(64 Class A) conventional zones and 48 (Form C) field programmable relay contact outputs.
The AX-CZM module mounts within an AXM-009 (see figure 44).
Refer to AX-CZM Installation Manual for detailed information regarding installation.
+
-
+
-
ZONE 1
ZONE 2
+
-
+
-
ZONE 3
ZONE 4
+
-
+
-
ZONE 5
ZONE 6
+
-
+
-
ZONE 7
ZONE 8
CLASS B ZONE MONITOR
ALL CIRCUITS ARE POWER LIMITED
ON
1
ON = PBUS MODULE
ON = CLASS A / OFF = CLASS B
ON = EARTH MONITOR ACTIVE
ADDRESS
SETUP
TX
RX
HB
COM
N/C
N/O
COM
N/C
N/O
COM
N/C
N/O
0V 24V
I/P MON
REL1 / FIRE
REL2 / TROUBLE
REL3 / EARTH
Zone Circuits (Class B or A)
Form C
Contact
Form C
Contact
Form C
Contact
24
VDC
A PBUS B
PBUS PWR
Suprv
Figure 43 - AX-CZM Module
Figure 42 – AX-RL4 AXM-009 Enclosure Mounting