5 Recommended Cable Routing
Power limited and non-power limited circuit wiring must remain separate in the fire alarm system enclosure. All
power limited circuit wiring must remain at least 0.25” (6.35 mm) away from any non-power limited circuit wiring.
Furthermore, all power limited and non-power limited circuit wiring must enter and exit the enclosure through
different knockouts and/or conduits (see figure 46).
Below is a typical diagram for the Axis
AX
;
AX-CTL-1L, AX-CTL-2 and AX-CTL-4 to meet the above mentioned power
limited wiring requirements:
LI
N
E
1
H
EAR
TB
EA
T
LI
N
E
2
SY
S
TR
O
U
B
LE
+
+
-
-
A
B
1
2
3
4
5
N
C
C
N
O
Figure 46 - AX-CTL-1L, AX-CTL-2 or AX-CTL-4 Cable Routing