A1-User’s Manual
73
8.1.21
PID
No.
Name
Change during
operation
Range
Default
Page
40.01
PID function
X
0.
Disable
1.
Enable
0
144
40.02
PID reference
O
0.0 to 100.0 [%]
0.0 %
144
40.03
PID reference source
X
0.
AI1 (O)
1.
AI2 (OI)
2.
'40.02'
3.
Modbus
4.
Fieldbus
2
145
40.04
PID feedback source
X
0.
AI1 (O)
1.
AI2 (OI)
1
145
40.05
PID P gain
O
0.1 to 1000.0 [%]
100.0 %
145
40.06
PID I gain
O
0.0 to 3600.0 [Sec]
1.0 Sec
146
40.07
PID D gain
O
0.00 to 10.00 [Sec]
0.00 Sec
146
40.08
PID Err limit
O
0.0 to 100.0 [%]
100.0 %
146
40.09
PID output high limit
O
-100.0 to 100.0 [%]
100.0 %
146
40.10
PID output low limit
O
-100.0 to 100.0 [%]
0.0 %
146
40.11
PID output invert
X
0.
Disable
1.
Enable
0
146
40.12
PID scale factor
X
0.1 to 1000 [%]
100.0 %
146
40.13
Pre PID frequency
X
0.00 to 400.0 [Hz]
0.00 Hz
147
40.14
PID sleep frequency
X
0.00 to 400.0 [Hz]
0.00 Hz
147
40.15
PID sleep/wake up delay time
X
0.0 to 30.0 [Sec]
0.0 Sec
147
40.16
PID wake up frequency
X
'40.14' to 400.0 [Hz]
0.00 Hz
148
40.17
PID feedback monitor
-
0.0 to 100.0 [%]
-
148
40.18
PID output monitor
-
0.0 to 100.0 [%]
-
148