A1-User’s Manual
141
Defines the number of automatic fault resets at
'31.11' (Automatic reset item 2)
31.15 Earth Fault
0: Disabled
Range: 0.0 ~ 100.0 % in 0.1 %
Initial value: 0.0 %
Program to enable the Ground fault detection and its fault level as a percentage of rated
current
31.16 Supply phase loss
0: Disabled
Range: 0 ~ 30 Sec in 1 Sec
Initial value: 10 Sec
Enables & sets the time period to determine if an Input Phase Loss occurs. The VFD
monitors the ripple on the DC bus voltage and if it occurs for the programmed magnitude
and time period an Input Phase Loss fault will occur. The ripple on the DC bus will cause
heating to the DC Bus capacitors which will shorten their life.
31.17 Stall function
0: No Operation
1: VFD overload
2: Over voltage
3: VFD overload and Over voltage ----- Initial value
Select a overload or overvoltage restriction modes
Set 0: No Operation
Overload Restriction Mode=Off, Overvoltage Restriction Mode=Off
Set 1: VFD overload
Overload Restriction Mode=On, Overvoltage Restriction Mode=Off
Set 2: Over voltage
Overload Restriction Mode=Off, Overvoltage Restriction Mode=On
Set 3: VFD overload and Over voltage
Overload Restriction Mode=On, Overvoltage Restriction Mode=On
Related Parameters:
'31.18', '31.19'
31.18 Stall current limit
Range: 20.0 ~ 200.0 % in 0.1 %
Initial value: 150.0 % (HD), 120.0 % (ND)
Program the level for overload restriction of the VFD rated current