A1-User’s Manual
110
20.10 Jogging enable
0: Not selected ----- Initial value
1: Selected
2: DI1
3: DI2
4: DI3
5: DI4
6: DI5
7: DI6
8: DI7
9: DI8
Selects the method for a jog enable
Set 0: Not selected
Always off
Set 1: selected
Always on
Set 2~9 : DI1~ DI8
It works by digital input which is selected
20.11 Jogging 1 start source
See the parameter '20.10' (Jogging enable)
Selects the source for the activation of jogging function 1
Both of jogging sources have interlocked each other.
If one of the jogging operates, other jogging can’t operate
Set 0: Not selected
Always off
Set 1: selected
Always on
Set 2~9 : DI1~ DI8
It works by digital input which is selected
20.12 Jogging 2 start source
See the parameter '20.10' (Jogging enable)
20.13 Direction
0: Forward ----- Initial value
1: Reverse
Sets the direction of VFD to forward or reverse at keypad operation only