A1-User’s Manual
108
Set 4: 2 Wire 3
The source of the start and stop commands are selected by parameters
'20.03' (Ext1 in source 1)
and
'20.04' (Ext1 in source 2)
The state transitions of the source bits are interpreted as follows:
State of source 1
('20.03')
State of source 2
('20.04')
Command
0 -> 1
1
Start
Any
0
Stop
when
'20.04' (Ext1 in source 2)
is 0,
The start and stop keys on the control panel are disabled
Set 5: 3 Wire 1
The source of the start and stop commands are selected by parameters
'20.03' (Ext1 in source 1)
and
'20.04' (Ext1 in source 2)
The source selected by
'20.05' (Ext1 in source 3)
determines the direction
The state transitions of the source bits are interpreted as follows:
State of source 1
('20.03')
State of source 2
('20.04')
State of source 3
('20.05')
Command
0 -> 1
1
0
Start forward
0 -> 1
1
1
Start reverse
Any
0
Any
Stop
when
'20.04' (Ext1 in source 2)
is 0,
The start and stop keys on the control panel are disabled
Set 6: 3 Wire 2
The source of the start and stop commands are selected by parameters
'20.03' (Ext1 in source 1), '20.04' (Ext1 in source 2)
and
'20.05' (Ext1 in source 3)
The source selected by
'20.05' (Ext1 in source 3)
determines the direction
The state transitions of the source bits are interpreted as follows:
State of source 1
('20.03')
State of source 2
('20.04')
State of source 3
('20.05')
Command
0 -> 1
Any
1
Start forward
Any
0 -> 1
1
Start reverse
Any
Any
0
Stop
Set 7: Modbus
The start and stop command are taken from terminal RXP-RXN
Set 8: Fieldbus
The start and stop command are taken from fieldbus adapter
Set 9: Keypad
The start and stop command are taken from keypad on the VFD