A1-User’s Manual
111
8.2.10
Start/Stop mode
21.01 Torque boost mode
0: Manual torque boost ----- Initial value
1: Automatic torque boost
Select a torque boost mode
It is working only V/F mode at
'98.01' (Motor control mode)
and will compensate for
starting torque.
If
'21.01' (torque boost mode) = 1
, recommended the following
1.
Put the plate data of motor in
'99.01' ~ '99.07'
2.
Get the motor data by the Auto Tuning
3.
Use auto tuning data at
'99.09' (Motor data selection)
21.02 Magnetization time
Range: 0.0 ~ 3000 Sec in 0.1 Sec
Initial value: 0.0 Sec
Set the time for DC Injection Braking duration before VFD start
It will be operated when
'21.02' (Magnetization time)
and
'21.03' (Magnetization level)
have set above zero
ON
Run command
Free run
21.02 (Magnetization time)
DC current
Frequency
Frequency
AC current
21.03 (Magnetization level)
21.03 Magnetization Level
Range: 0.0 ~ 200.0 % in 0.1 %
Initial value: 30.0 %
Set the level for DC Injection Braking duration before VFD start
21.04 Stop mode
0: Ramp to Stop (Deceleration) ----- Initial value
1: Coast to Stop (Free Run to Stop)
Select a stop method when Stop command is given.