5. Setting up the device
23
Menu level
Parameterisation level
Selection analog output,
Ou2.rA:
Default:
4-20
3 output signals are available 0-10 VDC, 0-20 mA and 4-20 mA. Select the desired signal with
this function.
Setting the final value of the analog output,
Ou2.En:
Default:
10000
The final value is adjusted from the smallest to the highest digit with
[
▲
] [
▼
]
and confirmed
digit per digit with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Setting the initial value of the analog output,
Ou2.of:
Default:
00000
The initial value is adjusted from the smallest to the highest digit with
[
▲
] [
▼
]
and confirmed
digit per digit with
[P]
. A minus sign can only be parameterised on the highest digit. After the
last digit the device changes back into menu level.
Overflow behaviour,
Ou2.fl:
Default:
edge
To recognise and evaluate faulty signals, e.g. by a controller, the overflow behaviour of the
analog output can be defined. As overflow can be seen either
EdGE
, that means the analog
output runs on the set limits e.g. 4 and 20 mA, or
to.OFF
(input value smaller than initial value,
analog output switches on e.g. 4 mA),
to.End
(higher than final value, analog output switches on
e.g. 20 mA). If
to.MIn
or
to.MAX
is set, the analog output switches on the smallest or highest
possible binary value. This means that values of e.g. 0 mA, 0 VDC or values higher than 20 mA
or 10 VDC can be reached. With
[P]
the selection is confirmed and the device changes into
menu level.
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group level
„–ou2–“
.