5. Setting up the device
25
Menu level
Parameterisation level
Alarms for relay 1,
CoM-1:
Default:
a.i
The allocation of the alarms to relay 1 happens via this parameter, one alarm or a group of
alarms can be chosen. With
[P]
the selection is confirmed and the device changes into menu
level.
Alarm relay 5,
reL-5:
The same applies for relays 6-8
Default:
al-5
Each setpoint (optional) can be linked up via 4 alarms (by default). This can either be inserted
at activated alarms
AL6/8
or deactivated alarms
ALN6/8
. If
LOGIC
is selected, logical links are
available in the menu level
LoG-1
and
CoM-1
. Access to these two menu levels is via
LOGIC
, at all
other selected functions, these two parameters are overleaped. Via
On/OFF
the setpoints can be
activated/deactivated, in this case the output and the setpoint display are set/not set on the
front of the device. The parameters
Cal
,
Cal.of
and
CAL.en
can only be used in accordance with
the semi-automatic calibration (
Chapter 9. Sensor alignment
). At
Cal
the relay switches during
sensor calibration, at
cal.of
during offset calibration and at
Cal.en
during the calibration of the
final value. With
[P]
the selection is confirmed and the device changes into menu level.
Logic relay 5,
LoG-5:
Default:
or
Here, the switching behaviour of the relay is defined via a logic link, the following schema
describes these functions with inclusion of
AL-1
and
AL-2
:
A1
v
A2
As soon as a selected alarm is activated, the relay
operates. Equates to operating current principle.
A1
v
A2 = A1
Λ
A2
The relay operates only, if no selected alarm is
active. Equates to quiescent current principle.
A1
Λ
a2
The relay operates only, if all selected alarms are
active.
A1
Λ
A2 = A1
v
A2
As soon as a selected alarm is not activated, the
relay operates.
With
[P]
the selection is confirmed and the device changes into menu level.
____ _ _
____ _ _
….
….
….