MAINTENANCE INTRODUCTION
Version 1.0
Acme Packet, Inc. Technical Publications
73
Power Supply Removal and Replacement
This section explains how to remove and replace the power supplies in the Net-Net
6300. This section is for both AC and DC power supplies.
Note:
There is an ESD receptacle in the top left corner in the rear of the
Net-Net 6300.
Caution
Turn the power source off before you remove or install the
power supply into the chassis.
The power supply is a user-replaceable component. If a Net-Net 6300 power supply
malfunctions you should remove the malfunctioning power supply and replace it.
The power supply can be removed from the chassis while still installed in the rack
and while the second power supply is providing system power; this is called a warm
swap.
Caution
Both power supplies must be the same type AC or DC. The Net-
Net SBC power supplies must be populated with two identical
power supplies made by the same vendor. The vendor is
identified by the label on top of the power supply.
Summary of Contents for Net-Net 6300
Page 6: ...vi Net Net 6300 System Hardware Installation Guide Version 1 0...
Page 9: ...ABOUT THIS GUIDE Version 1 0 Acme Packet Inc Technical Publications ix...
Page 10: ...x Net Net 6300 Hardware Installation Guide Version 1 0 ABOUT THIS GUIDE...
Page 26: ...24 Net Net 6300 Hardware Installation Guide Version 1 0 COMPONENT OVERVIEW...
Page 34: ...30 Net Net 6300 Hardware Installation Guide Version 1 0 GRAPHIC DISPLAY...
Page 102: ...100 Net Net 6300 Hardware Installation Guide Version 1 0 MAINTENANCE INTRODUCTION...
Page 106: ...100 Net Net 6300 Hardware Installation Guide Version 1 0 SAFETY...
Page 116: ...110 Net Net 6300 Hardware Installation Guide Version 1 0 GLOSSARY...