background image

 

 

18

8.7

 

ALARMS

 

Alarm

 

type

 

Alarm

 

description

 

Cause

 

Water

 

flows

 

alarm

 

Lack

 

of

 

water

 

circulation

 

on

 

the

 

hydraulic

 

side

 

of

 

the

 

heating/cooling/sanitary

 

boiler

 

system.

 

Hydraulic

 

pump

 

is

 

off,

 

burnt,

 

ecc.. the

 

pressure

 

of

 

the

 

water

 

side

 

is

 

zero

 

bar.

 

The

 

faucet

 

for

 

interception

 

of

 

the

 

system

 

are

 

closed.

Outdoor

 

unit

 

link

 

alarm

 

A

 

lose

 

or

 

bad

 

serial

 

connection

 

between

 

indoor

 

and

 

outdoor

 

moto

condensing

 

unit.

 

Electrical

 

connections

 

reversed

 

or

 

interrupted

 

Sensor

 

alarm

 

Bad

 

detection

 

of

 

the

 

temperature

 

sensor.

 

Cable

 

of

 

temperature

 

sensor

 

is

 

interrupted.

 

Temperature

 

sensor

 

error.

 

Water

 

antifreeze

 

Temperature

 

of

 

the

 

water

 

of

 

cooling/heating/sanitary

 

boiler

 

system

 

is

 

below

 

the

 

set

 

point.

 

Hydraulic

 

pump

 

is

 

off,

 

burnt,

 

etc...

 

Pressure

 

on

 

the

 

water

 

side

 

is

 

0

 

bar.

 

Faucets

 

for

 

the

 

interception

 

of

 

the

 

system

 

are

 

closed

 

8.8

 

ADJUSTMENT

 

OF

 

SANITARY

 

WATER

 

VALVE

 

To

 

activate

 

the

 

sanitary

 

hot

 

water

 

you

 

must:

 

 

connect

 

to

 

the

 

terminals

 

IA2

 

–G

 

a

 

sensor

 

which

 

should

 

be

 

installed

 

inside

 

the

 

tank,

 

 

connect

 

the

 

3

way

 

switch

over

 

valve

 

to

 

the

 

terminals

 

UD1

N

 

(with

 

spring

 

return)

 

If

 

the

 

sanitary

 

hot

 

water

 

temperature

 

is

 

lower

 

than

 

the

 

set

point

 

of

 

sanitary

 

water

 

(set

 

to

 

48°C

 

by

 

default)

 

the

 

unit

 

activates

 

the

 

3

way

 

switch

over

 

valve

 

to

 

deviate

 

the

 

flow

 

of

 

water

 

towards

 

the

 

water

 

tank

 

or

 

to

 

a

 

heat

 

exchanger.

 

If

 

the

 

set

point

 

of

 

sanitary

 

water

 

is

 

reached,

 

the

 

valve

 

returns

 

in

 

rest

 

period.

 

Contact

 

UD1

 

N

(3

way

 

valve):

 

 

close:

 

valve

 

energized

 

and

 

water

 

flow

 

deviated

 

to

 

the

 

water

 

tank,

 

 

open:

 

valve

 

de

energized

 

and

 

water

 

flow

 

deviated

 

to

 

the

 

user.

 

Commutating

 

from

 

winter

 

mode

 

operation

 

to

 

sanitary

 

mode

 

operation,

 

the

 

compressor

 

remains

 

on

 

and

 

works

 

under

 

the

 

set

 

frequency.

 

Commutating

 

from

 

summer

 

mode

 

operation,

 

the

 

compressor

 

turns

 

off

 

for

 

safety

 

period.

 

NOTES:

 

Using

 

the

 

keyboard

 

on

 

the

 

unit

 

to

 

turn

 

off

 

it

 

does

 

not

 

the

 

sanitary

 

operation

 

The

 

display

 

board

 

on

 

the

 

unit

 

shows:

 

 

In

 

sanitary

 

mode:

 

the

 

display

 

shows

 

the

 

temperature

 

measured

 

by

 

the

 

sensor

 

located

 

in

 

the

 

container,

    

 

In

 

heating

 

or

 

cooling

 

mode:

 

the

 

diplay

 

shows

 

the

 

outlet

 

water

 

temperature

 

sensor.

    

The

 

defrost

 

during

 

heating

 

operation

 

is

 

always

 

performed

 

on

 

the

 

user

 

side,

 

never

 

on

 

the

 

sanitary

 

water

 

tank.

 

9

 

MICROPROCESSOR

 

USER

 

INTERFACE

 

 

 

 

It

 

is

 

used

 

to

 

reset

 

the

 

manual

 

resetting

 

alarms.

 

During

 

the

 

parameters’

 

setting,

 

this

 

button

 

can

 

be

 

used

 

to

 

revert

 

BACK

 

to

 

the

 

previous

 

level.

 

 

It

 

allows

 

you

 

to

 

view

 

the

 

setting

 

menu

 

parameters.

 

 

UP

 

button:

 

In

 

the

 

setting

 

mode,

 

this

 

button

 

allows

 

you

 

to

 

move

 

up

 

to

 

a

 

higher

 

menu

 

or

 

to

 

increase

 

the

 

value

 

of

 

a

 

parameter

 

when

 

you

 

are

 

in

 

the

 

edit

 

mode.

 

 

DOWN

 

button:

 

In

 

the

 

setting

 

mode,

 

this

 

button

 

allows

 

you

 

to

 

shift

 

to

 

a

 

lower

 

menu

 

or

 

to

 

decrease

 

the

 

value

 

of

 

a

 

parameter

 

when

 

you

 

are

 

in

 

the

 

edit

 

mode.

 

 
 
 

Summary of Contents for PACK DUE 12

Page 1: ......

Page 2: ...the model 16 and we updated the dimensions of the packing of the models 12 and 16 In the section 15 the curve is updated The section 17 is improved with descriptions more clear and tables Wiring diag...

Page 3: ...DRAULIC CIRCUIT 9 4 11 FAN SPEED CONTROLLER 9 5 AVAILABLE VERSIONS 9 5 1 ACCESSORIES 9 6 INSTALLATION 9 6 1 GENERALITY 9 6 2 LIFTING AND HANDLING 10 6 2 1 INDOOR UNIT 10 6 2 2 OUTDOOR UNIT 10 6 3 LOCA...

Page 4: ...19 9 5 POWER FAILURE 19 9 6 ALARMS LIST 20 10 SHUTDOWNS FOR LONG PERIODS 20 11 MAINTENANCE AND PERIODIC CHECKS 20 11 1 ENVIRONMENTAL PROTECTION 21 12 WHEN THE UNIT GOES OUT OF SERVICE 21 13 TECHNICAL...

Page 5: ...OOR UNITS 36 21 1 INDOOR UNIT 36 21 2 OUTDOOR UNIT 36 22 WIRING DIAGRAMS 37 22 1 22 2 22 2 1 22 2 2 22 2 3 23 SOLAR MODULE OPTIONAL ACCESSORY 41 23 1 23 2 WIRING DIAGRAM 42 ASSEMBLY 41 OUTDOOR UNITS 3...

Page 6: ...00 6 1 Rule EN CEI 61000 6 3 Rule 97 23 CE 2006 95 CE 2004 108 CE 2002 95 CE Community Directives 3 GENERAL SAFETY GUIDELINES equipment and its controls and has to have read and understood the informa...

Page 7: ...he work place shall be provided so as to allow the operator to carry out the required operations safely Poor or too strong lighting can cause risks Ensure that work places are always adequately ventil...

Page 8: ...TWA 1000 ml m for each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator apparatus The vapors are heavier than air and ca...

Page 9: ...l overload protection The protection class of the motors is IP 54 4 5 FANS The fans are axial type with aluminium aerofoil blades They are statically and dynamically balanced and supplied complete of...

Page 10: ...xt chapters MUST BE DONE BY TRAINED PEOPLE ONLY Before any operation on the unit be sure that the electric supply is disconnected 6 1 GENERALITY When installing or servicing the unit it is necessary t...

Page 11: ...s also possible to install anti vibration supports springs or rubbers to keep vibrations at a very low level Absolute care has to be taken to ensure adequate air volume to the condenser Re circulation...

Page 12: ...espondence with the connection labelled WATER INLET otherwise the evaporator may freeze It is compulsory to install on the WATER INLET connection a metallic filter with a mesh not larger than 1 mm Sho...

Page 13: ...CONNECTION 6 4 4 1 INDOOR UNIT The indoor units are designed so that the base in which there are connections to the same act of the water tray Connect a pipe to the predisposed joint on the unit cfr C...

Page 14: ...working near them even if the unit is off The temperatures of heads and exhaust piping of the compressor are usually high Therefore be careful when working near condensing coils The aluminum fins are...

Page 15: ...cable supplied with the solar expansion kit fitting A3 Output 230Vac 1A MAX for resistance R2 of contactor control KM2 UD0 N For the connection please use a cable with a minimum section of 1 5mm YV1 3...

Page 16: ...pplicable regulations including grounding The voltage must be specified on the nameplate of the unit Ensure that the voltage is within the tolerance limits of 10 Check that the heating elements of the...

Page 17: ...ulic pump of solar system 8 2 FUNCTIONS OF BUTTONS Esc Alarm reset Menu exit User menu scrolling MODE ON OFF Change in heat pump mode To power on and off the heat pump Prg To select parameters To stor...

Page 18: ...heating Production of hot water for heating Heating and sanitary water Production of hot water for heating and sanitary hot water Only sanitary water Production of sanitary hot water 8 4 1 OPERATION...

Page 19: ...er towards the water tank or to a heat exchanger If the set point of sanitary water is reached the valve returns in rest period Contact UD1 N 3 way valve close valve energized and water flow deviated...

Page 20: ...1 Sensor alarms The alarm will be activated in the case of a short or open circuit of any connected and enabled sensor The alarm will be activated also when the temperature becomes higher than the se...

Page 21: ...unds Be very careful when operating in their surroundings After servicing operations re install the cover panels and fix them by means of screws The refrigerant circuits must not be filled with refrig...

Page 22: ...gerant R410A is mentioned among controlled substances and for this reason it has to be subjected to the mentioned norms A particular care is recommended during service operations in order to reduce as...

Page 23: ...depth condenser mm 778 660 38 1 758 813 44 887 1220 44 887 1220 44 Condenser Number of circuits 2 2 8 8 Type R410A R410A R410A R410A Refrigerant charge 5 kg 1 60 1 80 3 30 4 20 Refrigerant Pressure de...

Page 24: ...Refrigerant circuit Gas side connection inch 1 2 SAE 5 8 SAE 5 8 SAE 5 8 SAE Power input kW 3 0 3 0 4 0 4 0 Integrative resistance Current input A 13 10 13 10 17 40 17 40 Dimensions L A P mm 515 816 2...

Page 25: ...pondingly with the working data indicated above 0 10 20 30 40 50 60 70 0 6 0 8 1 1 2 1 4 1 6 1 8 2 2 2 2 4 2 6 2 8 3 Flowrate m 3 h Head Pressure Kpa 07 12 09 16 Optimum operating point for PACK DUE 7...

Page 26: ...utlet temperature C air temp 45 C air temp 40 C air temp 35 C air temp 30 C 6 7 8 9 10 11 12 13 14 15 16 17 18 19 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 Input power in cooling operation kW Water outl...

Page 27: ...49 51 53 55 57 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 Input power in heating operation kW Water outlet temperature C air temp 21 C air temp 14 C air temp 7 C air temp 0 C air temp 7 C...

Page 28: ...11 12 13 14 15 16 17 18 19 1 8 1 9 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 Input power in cooling operation kW Water outlet temperature C air temp 45 C air temp 40 C air temp 35 C air temp 30 C 6 7 8 9 10 11...

Page 29: ...mp 10 C 33 35 37 39 41 43 45 47 49 51 53 55 57 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 Coefficient of performance W W Water outlet temperature C air temp 21 C air temp 14 C air temp 7 C air temp 0...

Page 30: ...1 12 13 14 15 16 17 18 19 2 6 2 7 2 8 2 9 3 0 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 Input power in cooling operation kW Water outlet temperature C air temp 30 C air temp 35 C air temp 40 C air temp 45 C...

Page 31: ...3 45 47 49 51 53 55 57 2 9 3 3 3 7 4 1 4 5 4 9 5 3 5 7 Input power in heating operation kW Water outlet temperature C air temp 27 C air temp 20 C air temp 13 C air temp 7 C air temp 2 C air temp 2 C a...

Page 32: ...13 14 15 16 17 18 19 3 1 3 3 3 5 3 7 3 9 4 1 4 3 4 5 Input power in cooling operation kW Water outlet temperature C air temp 30 C air temp 35 C air temp 40 C air temp 45 C 6 7 8 9 10 11 12 13 14 15 16...

Page 33: ...57 2 7 3 0 3 3 3 6 3 9 4 2 4 5 4 8 5 1 5 4 5 7 6 0 6 3 Input power in heating operation kW Water outlet temperature C air temp 27 C air temp 20 C air temp 13 C air temp 7 C air temp 2 C air temp 2 C...

Page 34: ...phases of the system In all cases the maximum electrical input occurs for the heat pump operating mode at a water outlet temperature of 55 C and with outdoor temperature of 10 C see the tables in para...

Page 35: ...7 8 0 98 0 99 1 05 1 12 30 14 1 0 97 0 98 1 10 1 22 40 22 3 0 965 0 97 1 14 1 25 50 33 8 0 955 0 965 1 2 1 33 CCF Capacity correction factor IPCF Input power correction factor WFCF Water flow rate cor...

Page 36: ...the bottom of the unit Remove the cabinet 20 2 OUTDOOR UNIT Remove the connection screws connecting the top panel and the front panel Remove the top panel Remove the screws connecting the front right...

Page 37: ...witch 8 Expansion vessel 9 Pump 10 Heater collector 11 Manual air vent valve 21 2 OUTDOOR UNIT 1 Condensor coil assy 2 Fan motor support 3 Fan motor 4 Fan 5 Transductor 6 Expansion valve 7 Coil of the...

Page 38: ...ntegration resistance and sanitary boiler anti legionnaires BT3 Sanitary water sensor for boiler TH1 Ambient thermostat BT4 Outdoor air temperature sensor THS1 Resistance R1 of safety thermostat actio...

Page 39: ...38 22 2 OUTDOOR UNITS 22 2 1 Wiring diagram of PACK DUE 9...

Page 40: ...39 22 2 2 Wiring diagram of PACK DUE 12...

Page 41: ...40 22 2 3 Wiring diagram of PACK DUE 16...

Page 42: ...ION BOARD IN THE FOUR HOLES OF THE ELECTRIC BOX OF THE INDOOR UNIT AS SHOWN IN THE FRAME C REMOVE THE FOUR SCREWS OF THE CONTROL PANEL WITH A SPECIAL SCREWDRIVER D REMOVE THE CONTROL PANEL TOWARDS LEF...

Page 43: ...ly term inals ground live n eutral m ax 1 5 m m For the conne ction use a cable with a m axim um and m inim um section of 1 5 m m Follow the regulations for the section of the cable E2 Sollar collecto...

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Tel 071 723991 Fax 071 7133153 Web Site www accorroni it E mail a2b a 2 b it A2B Accorroni E G S r l Via d Ancona 37 60027 Osimo An...

Reviews: