13
•
Locate
the
hole
at
the
base
of
the
unit
between
the
finned
coil
and
fan,
A.
•
Connect
to
the
hole
the
provided
fitting
joint,
B.
•
Connect
a
hose
to
the
nozzle
of
the
supplied
fitting
joint.
•
Direct
the
hose
into
thedisposal
place
for
condensate
water.
•
Maintain
a
sufficient
slope
to
ensure
the
smooth
flow
of
condensate
water.
6.5
REFRIGERANT
DIAGRAM
SE
EEV
LR
IN
OUT
4WV
DT
LP
HP
ST
M
P
C
LS
OS
FL
FL
NRV
CLS
Pr
C
COMPRESSOR
CLS
COMPRESSOR
LIQUID
SEPARATOR
(only
for
the
models
i
‐
SHWAK/WP
05,
07
e
10)
OS
OIL
SEPARATOR
(only
for
the
models
i
‐
SHWAK/WP
10
e
15)
ST
COMPRESSOR
INLET
TEMPERATURE
DT
COMPRESSOR
OUTLET
TEMPERATURE
HP
HIGH
PRESSURE
TRANSDUCER
Pr
HIGH
PRESSURE
FLOW
SWITCH
LP
LOW
PRESSURE
TRANSDUCER
LS
LIQUID
SEPARATOR
(only
for
models
i
‐
SHWAK/WP
10
e
15)
4WV
VALVE
FO
INVERTING
CYCLE
LR
LIQUID
RECEIVER
EEV
ELECTRONIC
EXPANSION
VALVE
NRV
NO
RETURN
VALVE
(only
for
the
models
i
‐
SHWAK/WP
10
e
15)
FL
FILTER
M
AXIAL
FAN
SE
OUTDOOR
AIR
TEMPERATURE
P
CIRCULATOR
ON
BOARD
UNIT
IN
WATER
INLET
TEMPERATURE
OUT
WATER
OUTLET
TEMPERATURE
WARNING:
The
unit
should
be
installed
so
that
adequate
clearance
is
available
for
maintenance
and
repairation.
The
warranty
does
not
cover
costs
related
to
platforms
or
handling
equipment
necessary
for
any
maintenance.
All
maintenance
and
testing
operations
should
be
carried
out
only
by
QUALIFIED
PERSONNEL.
Before
any
operation
on
the
unit,
make
sure
the
power
supply
is
disconnected.
WARNING:
Inside
the
unit,
there
are
some
moving
parts.
Be
especially
careful
when
working
near
them,
even
if
the
unit
is
off.
The
temperatures
of
heads
and
exhaust
piping
of
the
compressor
are
usually
high.
Therefore
be
careful
when
working
near
condensing
coils.
The
aluminum
fins
are
very
sharp
and
can
cause
serious
injuries.
After
the
maintenance
operations,
close
the
panels
tightly
with
the
fastening
screws.
6.6
ELECTRICAL
CONNECTIONS
Check
out
that
the
power
supply
meets
the
unit’s
electric
nominal
data
(tension,
phases,
frequency)
reported
on
the
label
in
the
unit’s
front
panel.
Power
connections
have
to
be
made
in
accordance
to
the
wiring
diagram
enclosed
with
the
unit
and
in
accordance
to
the
national
and
international
norms
in
force.
Power
cables
and
line
fuses
have
to
be
sized
according
to
the
specifications
listed
in
the
wiring
diagram
enclosed
with
the
unit.
WARNING:
The
supply
voltage’s
fluctuations
can
not
exceed
±10%
of
the
nominal
value.
Should
these
tolerances
not
be
respected,
please
contact
our
technical
department.
WARNING:
The
power
supply
have
to
respect
the
listed
limits:
failing
this,
warranty
will
terminate
immediately.
Before
any
operation
on
the
unit,
be
sure
that
the
power
supply
is
disconnected.
WARNING:
The
water
flow
switch
(the
component
number
5
in
the
previous
image
and
factory
installed)
have
ALWAYS
to
be
connected
following
the
indications
listed
in
the
wiring
diagram.
Never
bridge
the
water
flow
switch
connections
in
the
terminal
board.
Should
the
water
flow
switch
connections
altered
or
not
properly
made,
the
guarantee
will
be
invalidated.
WARNING:
The
indoor
unit
can
not
be
installed
in
areas
with
strong
vibrations,
corrosive
gases,
and
excess
of
dirtiness
or
high
humidity
levels.
Comply
with
the
minimum
technical
installation.