33
17
OPERATION
LIMITS
17.1 Evaporator water flow rate
The
nominal
water
flow
rate
is
referred
to
a
∆
T
=
5°C,
between
the
evaporator’s
inlet
and
outlet
temperatures.
The
allowed
maximum
flow
rate
is
corresponding
to
∆
T
=
3°C;
higher
values
may
cause
too
high
pressure
drops.
The
allowed
minimum
water
flow
rate
is
corresponding
to
∆
T
=
8°C.
Insufficient
values
may
cause
too
low
evaporating
temperatures
with
the
intervention
of
safety
devices
which
would
stop
the
unit
and,
in
some
particular
cases,
the
water
can
freeze
in
the
evaporator
coil
causing
the
refrigeration
circuit
to
break
down.
We
enclosed
below
a
most
accurate
table
showing
the
minimum
flow
rates
that
to
ensure
for
the
plate
heat
exchanger
for
a
the
proper
operation
of
unit
according
to
the
model
(note:
the
water
flow
switch
is
used
for
preventing
the
freezing
sensor
from
failure
in
the
case
of
insufficient
water
flow
but
it
does
not
ensure
the
minimum
flow
rate
required
in
order
the
unit
can
work
properly)
Model
Cooling
capacity
for
reference
[kW]
6,12
8,12
11,90
14,07
Minimum
water
flow
rate
that
to
ensure
[L/s]
0,183
0,243
0,356
0,421
As
a
first
approch,
and
in
the
absence
of
other
detection
systems,
the
proper
flow
rate
for
getting
the
best
performance
from
your
unit
can
be
found
at
maximum
speed
of
the
circulator,
using
the
pressure
gauges
for
controlling
the
pressure
difference
between
the
return
and
the
delivery
water
on
the
outside
water
connections
of
the
unit
and
make
sure
that
such
value
is
equal
or
less
than
the
static
pressure
indicated
on
the
curves
shown
in
paragraph
16
for
the
respectives
models.
17.2 Cold water temperature (summer operation)
The
allowed
minimum
temperature
at
the
evaporator’s
outlet
is
5°C;
for
more
lower
temperatures,
the
unit
should
undergo
some
necessaries
structural
modifications.
In
this
case
contact
our
company
for
the
feasibility
study
and
evaluation
of
changes
to
be
made
according
to
your
requests.
The
maximum
temperature
that
can
be
maintained
at
the
outlet
of
the
evaporator
is
25°C.
Higher
temperatures
(up
to
a
maximum
of
40°C)
can
anyway
be
tolerated
during
transitions
and
start
‐
up
phases
of
the
system.
In
all
cases,
the
maximum
electrical
input
occurs
for
the
heat
pump
operating
mode
at
a
water
outlet
temperature
of
55°C
and
with
outdoor
temperature
of
‐
10°C
(see
the
tables
in
paragraph
17.3).
17.3 Hot water temperature (winter operation)
Once
the
system
is
working
at
the
right
temperature,
the
inlet
hot
water
temperature
should
not
to
be
lower
than
25°C;
the
lowest
values
that
are
not
related
to
transitional
or
start
‐
up
stages
may
cause
compressor’s
incorrect
working
operation
and
its
possible
related
breakdown.
The
maximum
outlet
water
temperature
have
not
to
exceed
55°C.
As
a
function
of
the
maximum
input
power
and
the
consequent
performance
decrease
in
terms
of
C.O.P.
outlet
temperature
of
the
water
up
to
55°C
with
outdoor
air
temperature
up
to
5°C
are
basically
recommended.
The
water
outlet
temperature
may
be
reduced
for
lower
temperatures
of
the
outdoor
air
temperature,
this
is
according
to
the
conditions
of
use,
taking
account
of
the
consumption
values
indicated
in
the
tables
below
for
the
maximum
input
power
as
a
function
of
the
outdoor
temperature
and
the
produced
water.
For
higher
temperatures
than
those
pointed
out,
especially
if
have
a
concomitant
with
the
reduction
of
the
water
flow
rate,
it
may
cause
abnormalities
to
the
normal
operating
of
the
unit,
or
the
safety
devices
act
in
critical
cases.
Temperature
of
produced
water
55°C
Model
Outdoor
temp.
°C
Input
(kW)
Input
(kW)
Input
(kW)
Input
(kW)
+
5
2,25
2,95
4,84
5,42
‐
10
2,36
3,04
5,65
6,21
Temperature
of
produced
water
50°C
Model
Outdoor
temp.
°C
Input
(kW)
Input
(kW)
Input
(kW)
Input
(kW)
+
5
2,01
2,68
4,36
4,96
‐
10
2,10
2,74
5,31
5,53
Temperature
of
produced
water
45°C
Model
Outdoor
temp.
°C
Input
(kW)
Input
(kW)
Input
(kW)
+
5
1,79
2,42
3,98
4,58
‐
10
1,88
2,49
4,97
5,24
17.4 Ambient air temperature
The
units
are
designed
and
manufactured
to
operate,
in
summer
operation,
with
the
condensate
control,
with
outdoor
air
temperatures
ranging
between
‐
10°C
and
46°C.
While
operating
as
a
heat
pump,
the
admitted
outdoor
air
temperatures
range
from
‐
15°C
to
40°C
as
a
function
of
the
water
outlet
temperature
as
indicated
in
the
below
table.
PACK DUE 7
PACK DUE
9
PACK DUE
12
PACK DUE
16
PACK DUE
7
PACK DUE
9
PACK DUE
12
PACK DUE
16
PACK DUE
7
PACK DUE
9
PACK DUE
12
PACK DUE
16
PACK DUE
7
PACK DUE
9
Input
(kW)
PACK DUE
12
PACK DUE
16
Summary of Contents for PACK DUE 12
Page 1: ......
Page 39: ...38 22 2 OUTDOOR UNITS 22 2 1 Wiring diagram of PACK DUE 9...
Page 40: ...39 22 2 2 Wiring diagram of PACK DUE 12...
Page 41: ...40 22 2 3 Wiring diagram of PACK DUE 16...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......