1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 73
Trip Only
Forward and
Backward
From service connector (with Ekip Connect) or with system bus communication it is possible to
configure D protection (if available and enabled) with 2 further parameters:
Trip only Forward
: if activated, D protection manages opening commands only if a forward
direction is detected
Trip only Backward
: if activated, D protection manages opening commands only if a
backward direction is detected
A malfunction in the opposite direction is only managed for alarm information.
Type of
selectivity
From service connector (with Ekip Connect) or with system bus communication, for S, S2, G, D
protections (if available and enabled) it is possible to configure the zone selectivity inputs and
some outputs:
Standard:
operation as per standard zone selectivity logic (default configuration)
Custom:
in this mode it is possible to select the activation event of the zone selectivity input
or output.
IMPORTANT: in the Custom configuration the only event to activate zone
selectivity is the one set, and therefore the standard selectivity operation is not
active (change recommended only for expert technical staff)
Startup
The function, which can be activated for S, I, G, S2, D, and UP protections (if available and
enabled), allows modifying the protection threshold (
StartUp threshold
) for a period set by the
user (
Startup time
).
NOTE: for UP protection the startup is to be understood as the during which the
protection is disabled
The period is activated when a threshold is exceeded (activation threshold), programmable by
the user with Ekip Connect or system bus, valid and verified for all phase currents.
The Startup condition is extinguished after the Startup time and is reactivated the next time the
activation threshold is exceeded.
NOTE: startup does not reoccur while at least one current remains above the activation
threshold level
Below is a graphical representation with S protection:
Figure 25
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...