1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 142
Modes
Two operating modes are available, which can be configured from the menu:
Modes
Description
TCP
Modbus
Information and commands managed by single requests/questions, according to
mapping and rules of TCP Modbus protocol (see System Interface)
Server
HTTP
Information and commands available on a web page, which can be accessed by
a browser by inserting the IP Address of the module as the address.
The page has a login window requesting the user password to be entered that is
the same as the password required on the display to modify parameters.
Configurations
on menu
Activating the local bus is required to start communication between the module and Ekip Touch
and is available in the
Settings menu
(page 114).
If the module is detected correctly by Ekip Touch in the
Modules Settings
menu, the following
communication parameters can be configured:
Parameter
Description
Default
Function
Defines the mode between TCP Modbus and Server
HTTP
TCP Modbus
Static IP address
ON
Defines whether the module has a dynamic IP (Off)
address or static (On) IP address
If = On all the associated parameters are enabled
Off
Static IP address
Enables static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway
address
Enables, in the presence of several subnets the IP
address of the node to which the module is connected
to be selected
0.0.0.0
Information on
menu
If the module is detected correctly by Ekip Touch, the following information is available on the
About
-
Modules
menu:
Information
Description
SN and version
Identification and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at
the moment of the connection to the network in the event of
configuration with dynamic IP or can be set by menu in the case of a
static IP
NOTE: without a DHCP server, the module automatically
adopts a causal IP address in the interval 169.254.xxx.xxx
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which
the modules belong and enables modules to be searched for within a
defined set of recipients
Gateway address
IP address of the node to which the module is connected, in the
presence of several subnets
TCP Client 1, 2, 3
IP addresses of the client devices connected to the module (in Server
mode)
MAC Address
Address assigned by ABB with OUI (Organizationally Unique Identifier)
equal to ac:d3:64 that identifies uniquely the manufacturer of an
Ethernet device
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...