1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 167
Input
Parameters
All the available inputs enable the following parameters to be configured:
Parameter
Description
Default
Polarity
Defines whether the input is defined as ON by Ekip Touch when
it is open (
Active open
) or when it is closed (
Active Closed
)
Active
closed
Delay
Minimum duration of activation of the input before the status
change is recognized; the delay is expressed in seconds, which
are settable in a range: 0 s .. 100 s with 0.01 s step
NOTES:
if the source is deactivated before this time has
elapsed the status change is not recognized
with delay = 0 s the status change must be anyway
greater than 300
S
0.1 s
Parameters
Output
Parameter
Description
Default
Signal source
Event that activates the output and switches the contact.
On the display, different protection proposals, statuses and
thresholds are available; via Ekip Connect the Custom mode
can be configured to extend the solutions and combine several
events.
None
Delay
Minimum duration of presence of the source before the output
is activated; the delay is expressed in seconds, which are
settable in a range: 0 s .. 100 s with 0.01 s step
NOTES:
if the source is deactivated before this time the
output is not switched
with delay = 0 s the source must be anyway
present for more than 300
S
0 s
Contact type
Defines the rest status of the contact with a non-present source
between: open (NO) and closed (NC)
NO
Latched
Enables the output (and relative status LED) to be maintained
active (ON) or be deactivated (OFF) until the event disappears.
Off
Activation time
Minimum
Defines the minimum closure time of the contact following the
rapid presence of sources:
Source duration < min. activation= the contact is activated
for the minimum activation time
Source duration
min. activation=the contact is activated
for as long as the source persists
It is possible to choose between: 0 ms, 100 ms, 200 ms
0 ms
NOTE: if
Power Controller
function is active, the following considerations apply:
Latched: deactivate sall the Latched configuration of the outputs used for
Power
Controller
Minimum activation time: the
Power Controller
option is available in addition to
those that have already been described: if selected, the output and active latching
is active for a set time that depends on the function, regardless of the persistence
of the event that activated it.
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...