1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 198
Menu
information
If the module is correctly detected by Ekip Touch, the following information is available in the
Information-Modules
menu:
Information
Description
SN and version
Module identifier and SW version
IP address
Module address, assigned to the module by a DHCP server when connecting to
the network with a dynamic IP, or settable from the menu when using a static IP
NOTE: without a DHCP server, the module automatically adopts a
random IP address in the range 169.254.xxx.xxx
Network Mask
Identifies the method for recognizing the subnet to which modules belong, with
the possibility of searching for modules within a set of defined recipients
Gateway address
IP address of the node to which the module is connected when there are multiple
subnets
MAC address
Address assigned by ABB with OUI (Organizationally Unique Identifier) equal to
ac:d3:64 that uniquely identifies the manufacturer of an Ethernet device
Remote
configurations
From the service connector (via Ekip Connect) or with system bus communication it is also
possible to access additional parameters.
Parameter
Description
Default
Client/Server
Parameter to change the module configuration from Server Only to
Client and Server and integrate it into an interactive data exchange
network (see
Ekip Com Hub
on page 156)
IMPORTANT: if Client/Server, the module allows
data exchange as per normal Server operations
Server
only
Enable IEEE 1558
Enable the IEEE 1588 protocol for clock signal distribution and
synchronization
(1)
OFF
Master IEEE 1588
Set the module as a master in the network segment it belongs to
(synchronization clock)
OFF
IEEE 1588 delay
mechanism
Choose the mode of data exchange between module and master,
either Peer-to-Peer or End-to-End
End-to-
End
Enable SNTP client
Enable the SNTP protocol for clock signal distribution and
synchronization
(1)
OFF
SNTP Server
Address
Identify the network server that provides SNTP
0.0.0.0
Time zone
Defines the time zone to be used for synchronization
+00:00
Daylight Saving
Time
Specifies whether the local country uses daylight saving time (ON)
or not (OFF)
OFF
Disable Gratuitous
ARP
Enable (ARP Enabled) the periodic generation of a Gratuitous ARP
message, used by Ekip Connect to quickly find the modules with an
Ethernet scan without knowing the IP address in advance
ARP
enabled
Password protected
access
Protect the write operations carried out from the network with a
password (password required)
Standard
mode
Modbus TCP
password
With
password-protected access
enabled, it is the password to be
used before each write session
(2)
Local
access
NOTES:
(3)
IEEE 1558 and SNTP client
must not be enabled at the same time
(4) the parameter can only be changed via system bus in
remote
configuration
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...