1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 59
D Protection [2]
Parameter
Description
Default
Zone
Selectivity
Activates/deactivates the function and the display availability of
selectivity time, see page 71
for details
NOTE: for correct operation of selectivity D, configure
OFF selectivity S, S2 and G
OFF
Fw
selectivity
time
This is the trip time of the protection with the zone selectivity
function active, forward direction and selectivity input Fw not
present, see page 71for details
The value is expressed in seconds, which are settable in a range:
0.1 s .. 0.8 s, with 0.01 s step
0.13 s
Bw
selectivity
time
This is the trip time of the protection with the zone selectivity
function active, backward direction and selectivity input Bw not
present, see page 71for details
The value is expressed in seconds, which are settable in a range:
0.1 s .. 0.8 s, with 0.01 s step
0.13 s
StartUp
enable
Activates/deactivates the function and display availability of the
combined parameters, see page 73 for details
OFF
StartUp
threshold
Fw
Protection threshold valid during Startup time, in the conditions in
which the function is active and with forward current direction, see
page 73 for details
The value is expressed both as an absolute value (Ampere) and as
a relative value (In), settable in a range:
0.6 In .. 10In with 0.1 In step
2 In
StartUp
threshold
Bw
Protection threshold valid during Startup time, in the conditions in
which the function is active and with backward current direction,
see page 73 for details
The value is expressed both as an absolute value (Ampere) and as
a relative value (In), settable in a range:
0.6 In .. 10In with 0.1 In step
2 In
StartUp time
This is the time for which the StartUp threshold is active, calculated
from tripping of activation threshold, set details on page 73
The value is expressed in seconds, which are settable in a range:
0.1 s .. 30 s, with 0.01 s step
0.1 s
Min Angle
Direction
Ekip touch calculates the phase displacement angle between
measured reactive power and measured power: when the phase
displacement becomes greater than the set
Min Angle Direction
parameter, the unit considers the fault direction
The value is expressed in degrees, which are settable in a range of
15 values from 3.6 ° to 69.6 °
3.6 °
Constraints, limitations, and additional functions
From the service connector (with Ekip Connect) or with system bus communication it is also
possible to access the block functions, the selectivity type and the parameters Trip only
Forward and Trip Only Backward, see page 73.
Application notes
Activating D directional protection automatically activates the alarm that controls the phase
sequence (that can also be deactivated and activated manually). Notice that in the case of
a cyclical sequence of the phases different from the value set, directional protection
reverses the direction of reference in case of malfunction with respect to what was
expected. The details of phase sequence protection are available on page 48.
In the event of small over-currents the behavior of the directional protection is influenced
by the type of load. To avoid the possibility of an incorrect detection of the direction of the
malfunction current in the event of a capacitive load, it is suggested that the regulation of
this protection be referred to real malfunctions and not to overloads
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...