1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 75
Programmable
commands
Eight commands with programmable activation are available depending on signals or events.
Located in various Ekip Touch menus, the commands are:
Name
Description
Path (page)
External trip
Sends a TRIP command
Advanced -
Functions (27)
Trip RESET
Reset of the trip signal
Switch on SET B
Check protections set, from Set A to Set B
Energy RESET
Reset of energy counters
Measurements-
Energy (28)
YO Command
Sends an open command
; it’s necessary the
presence of MOE-E
Settings - Functions
(29)
YC Command
Sends a close command;
it’s necessary the
presence of MOE-E
Switch On LOCAL
Configuration change, from Remote to Local
Settings - Modules
-Functions (29)
Signalling RESET
Reset contacts of signalling modules
Parameters
Each command has two programmable parameters:
Parameter
Description
Default
Function
One or several events (up to eight, in AND or OR logic
configuration) to activate command.
The Custom configuration can be programmed via Ekip Connect
Deactivated
Delay
Is the minimum time of persistence of the event before the
command is sent; the value is expressed in seconds, which are
settable in a range: 0 s .. 100 s, with 0.1 s step
0 s
IMPORTANT: the commands are sent if all the operating conditions expected by
the units are found (connections, power supplies, alarms, etc.).
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...