1SDH002031A1002 ECN000092998 Rev. B
SACE Tmax XT2
– XT4 | 197
Programmable
Logic
With the Programmable Logic function it is possible to program the activation of up to four bits of
the
Ekip Link
, each bit according to any combination of the status bits of an actor whose IP
address has been entered.
These four bits are referred to as States A B C and D, remotely programmable, and their value
is transmitted to the device to which
Ekip Link
is connected
Power
Controller
With the
Power Controller
function each actor can:
Acquire the status and control the loads
Perform the role of master and gather the energy measurements of the actors included as
Energy Meter
Provide energy measurements to actors included as masters
The status of the loads can be acquired by checking the status of the inputs of the signaling
modules connected to the actors whose IP Addresses have been included, while the load control
can be performed by programming their outputs.
Remote acquisition of the load states and their control can also be performed with
Ekip Signalling
10K
s connected to the network.
More information on the potential of the function is available in White Paper 1SDC007410G0201
"Load management with Ekip Power Controller for SACE Emax 2."
Zone selectivity
With the Zone Selectivity function:
The IP addresses entered refer to the actors with interlocking role compared to the current
one
For each interlocking actor included the protections must be selected for which selectivity
must be implemented by setting a mask. The function thus configured is subsequently
referred to as logical, to distinguish it from the standard that later is also referred to as
hardware
The protections thus selected are added to the S, G, D-Backward and D-Forward hardware
ones
It is possible to choose between only hardware or both hardware and logical selectivity
It is possible to set the diagnostics to check for each interlock release if there is congruence
between the hardware and logical selectivity information
It is possible to set a mask that identifies the protections to which the selectivity information
received will be retransmitted, regardless of whether the actor is in an alarm state. The
mask is applicable only to information about logical selectivity
For more information on the Zone Selectivity function with
Ekip Link
, see page 76.
Supply
Ekip Link is powered directly by the Ekip Touch it is connected to.
NOTE: without an auxiliary power supply communication between Ekip Touch and the
module is interrupted
Menu
configurations
The activation of the local bus
– essential to start the communication between the module and
Ekip Touch
– is available in the
Settings
menu (page 29).
If the module is correctly detected by Ekip Touch, it is possible to configure the following
communication parameters in the
Settings-Modules
menu:
Parameter
Description
Default
Static IP address ON
Defines if the module has a dynamic IP address (Off) or static
(On). If = On all the associated parameters are enabled
Off
Static IP address
Enter the static IP address
0.0.0.0
Static Network Mask
Enter the subnet mask
0.0.0.0
Static gateway
address
With multiple subnets, enter the IP address of the node the
module is connected to
0.0.0.0
Summary of Contents for SACE Tmax XT2
Page 84: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 84 L curve Ekip M Touch S curve t k I2 ...
Page 86: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 86 G curve t k I2 G curve t k ...
Page 87: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 87 IU curve UV curve UV2 curve ...
Page 88: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 88 OV curve OV2 curve VU curve ...
Page 89: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 89 S V curve S2 V curve RV curve ...
Page 90: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 90 UF curve UF2 curve OF curve OF2 curve ...
Page 91: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 91 RP curve D curve ...
Page 92: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 92 OQ curve OP curve ...
Page 93: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 93 UP curve RQ curve ...
Page 94: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 94 ROCOF curve R JAM curve R STALL ...
Page 95: ...1SDH002031A1002 ECN000092998 Rev B SACE Tmax XT2 XT4 95 UC curve ...