I.L. 40-386.3
(10/94)
3-9
NOTE:
The setting of
∆
I,
∆
V, for OSC is not recommended since data will
be collected for normal operations.
3.3.2
Fault Data (Flt. Data) Capture Setting
Is for selecting one of the 3 ways (TRIP/Z2TR/Z2Z3) to initiate the fault data taken,
where:
TRIP – to store fault data only if trip action occurs.
Z2TR – to store fault data if Zone2 units pick up or any trip action occurs.
Z2Z3 – to store fault data if Zone2 or Zone3 units pick up or any trip action occurs.
3.3.3
Current Transformer Ratio Setting (CT Ratio)
The
CT Ratio
is used for the load current monitoring, if it is selected to be displayed
in primary amperes. It has no effect on the protective relaying system.
For this example, set
CT Ratio
= 240.
3.3.4
Voltage Transformer Ratio Setting (VT Ratio)
The
VT Ratio
is used for the system voltage monitoring, if it is selected to be displayed
in primary volts. It has no effect on the protective relaying system.
For example, set
VT Ratio
= 600.
3.3.5
Frequency Setting (Freq.)
Should be selected to match the power system operating frequency.
For example, select
Freq.
= 60 if the power system operating frequency is 60 Hertz.
3.3.6
Current Transformer Type Setting (CT Type)
Provides the flexibility for 5 amp or 1 amp rated current transformer selection.
For example, select and set
CT Type
= 5 if a 5 amp current transformer is used.
The setting of
CT Type
affects all the distance unit and overcurrent unit setting rang-
es. The ranges will be automatically changed as listed in
Table 3-1
:
3.3.7
Read Primary Setting (Read Out)
The Read Out should be set to Primary Units if all the monitoring ac voltages and currents are
selected to be displayed in primary KV and KA values, respectively.
3.3.8
Ohms Per Unit Distance (X / Dist)
The line reactance setting X / Dist is the multiplier for fault distance display. It has a range of
0.3 to 1.5 ohms (primary) in 0.001 steps. In this example, the line reactance is 0.8 ohms/mile;
set X / Dist = 0.8.
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...