I.L. 40-386.3
2-12
(10/94)
unless 21BI operates. This prevents operation of the distance relay on load. The OSB
signal is also applied to the reclosing logic for initiating RB.
The following quantities are used for the blinder sensing:
VXG
=
Phase to ground voltage, VAG or VBG
I
X
= Phase current in
φ
A or
φ
B
R
C
= Setting of the unit OS inner for 21BI (R
T
) or OS outer for 21BO (R
U
). RT for inner
blinder (21BI), RU for outer blinder (21BO).
PANG = The positive sequence line impedance angle. Setting of (Ang Pos.).
Operation occurs if the operating voltage leads the polarizing voltage. The character-
istics are as shown in
Figure 2-18b.
Blinder reaches are determined by the setting of OS inner and OS outer, respectively.
2.4.16.1
Subsequent Out-of-Step Security Logic
Model power system tests, when using a motor-generator-set, show that the Zone1 im-
pedance unit may overreach or respond to a reversed fault. This was attributable to
motor-generator set instability following delayed clearing on an external fault. The
Zone1 relay, in all cases, identified the fault location and type correctly and responded
much later to the swing condition.
Logic was added utilizing the inner blinder and Zone1 sensing sequence, plus a 50 ms
timing action
(as shown in Figure 2-18a)
, AND-131A, AND-131B, AND-131C and OR-
122A, to differentiate between a fault and a subsequent out-of-step condition. This
logic will not affect normal Zone1 trip time, nor will it affect normal out-of-step block-
ing.
2.4.17 Oscillographic Data
The oscillographic data has 8 samples per cycle, 1 cycle pre-trigger and 7 cycles post-
trigger. It includes 16 events and 24 digital intermediate targets (test points). The data
can be accessed via the communication port.
The oscillographic data is controlled by one of the following selections in the OSC Data
function:
Trip
(TRIP)
— data taken only if trip action occurs
Zone2
(Z2TR)
— data taken if Zone2 units pick up or any trip action occurs.
Blinder
Line
Polarizing
Operating
Left
-j(VXG + IXRC (PANG–90
°
) IX (PANG–90
°
)
Right
j(VXG - IXRC (PANG–90
°
) IX (PANG–90
°
)
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...