I.L. 40-386.3
(10/94)
2-9
2.4.8
Unequal-Pole-Closing-Load Pickup Logic
The ground units may pick up on a condition of load pickup with unequal breaker pole
closing. The high speed ground units (Zone1G, FDOG and PLTG) should be supervised
under this condition. This can be achieved
(as shown in Figure 2-16)
by inserting a 0/
20 ms timer (controlled by the 52b signal) to supervise the Zone1G trip AND-3. It
should be noted that the 20 ms time delay will have no effect on a normal fault clear-
ing.
2.4.9
Loss-of-Load Accelerated Trip Logic
NOTE:
The LLT function doesn’t need to be set for normal operation of the re-
lay. While it can provide faster tripping for end-Zone faults, it may not
be used in all situations. It should be applied with caution based on
thorough knowledge of the system characteristics where the relay is ap-
plied. It is definitely not applicable where maximum tapped load may
exceed minimum through-load in the protected line.
The load-loss speedup Zone2 trip logic senses remote 3-pole clearing on all faults ex-
cept 3 phase to complement or substitute for the action of the pilot channel, to speed
up trip at the slow terminal. Logic includes AND-24, AND-25, OR-13, 0/32, and 10/
0 ms timers
(as shown in Figure 2-17)
. Under normal system conditions, 3-phase load
currents are balanced, the low set overcurrent units (IAL, IBL, ICL satisfy both AND-
24 and OR-13). On remote internal faults,
Zone2 Phase (Z2P) or Zone2 Ground(Z2G)
picks-up and satisfies the third input to AND-25 via OR-6. However, the signal from
AND-24 is negated to AND-25, therefore, AND-25 should have no output until the re-
mote end 3-pole trips. At this time, the local end current will lose one or two phases,
depending on the type of fault (except for the 3-phase fault). The AND-24 output signal
changes from “1” to “0” and satisfies AND-25. After 10 ms, this output by-passes the
T2 timer, and provides speedup Zone2 trip. The (10/0 ms) time delay is for coordina-
tion on external faults with unequal pole clearing. The 0/32 ms timer is needed for
security on external faults without load current condition. Target
LL Trip (LLT)
will
turn on after an LL Trip. The
LL Trip (LLT)
function is selected by setting
LL Trip
“YES,
FDOG, NO”, where YES = LL Trip with Z2 supervision; FDOG = LL Trip with both Z2
and (FDOG/I
OM
) supervision; the NO = LL Trip function is not used.
2.4.10 Current or Voltage Change Fault Detector (
∆
I,
∆
V )
The REL 301/302 relay normally operates in the Background mode, where it experi-
ences phase current or voltage disturbances. During background mode, the four input
currents (IA, IB, IC and I
p
) and the three voltages (VA, VB, VC) are sampled at a rate
of 8 p e r c y c l e t o t e s t a l i n e f a u l t . W h e n a p h a s e d i s t u r b a n c e (
∆
I o r
∆
V )
i s d e t e c t e d , t h e r e l a y e n t e r s a f a u l t m o d e f o r s e v e r a l c y c l e s t o p e r f o r m
p h a s e a n d g r o u n d unit distance computation for each zone. The criteria for deter-
mining a disturbance in the REL 301/302 design are as follows:
1 )
E a c h p h a s e
∆
I :
i f [ I
K n
- I
( K - 1 ) n
] > 1 . 0 a m p .
A n d [ I
K n
- I
( K - 1 ) n
] / I
( K - 1 ) n
x 1 0 0 % > 1 2 . 5 %
2 )
E a c h p h a s e
∆
V :
i f [ V
K n
- V
( K - 1 ) n
] > 7 . 0 v o l t s
a n d [ V
K n
- V
( K - 1 ) n
] / V
( K - 1 ) n
x 1 0 0 % > 1 2 . 5 %
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...