I.L. 40-386.3
(10/94)
4-3
LED
Color
Condition
PROTECTION LEDS
PROTECTION IN SERVICE
Yellow
ON– For Normal condition of dc power
Successful self-check
Self-test routines
OFF – Any of the above failed
PILOT
Red
Pilot Tripped
Zone1
Red
Zone1 Tripped
Zone2
Red
Zone2 Tripped
Zone3
Red
Zone3 Tripped
AG
Red
AG Fault
BG
Red
BG Fault
CG
Red
CG Fault
M
φ
Red
Multi-phase Fault
OTHER
Red
Fault Generated by Overcurrent
Load Loss, or
Trip Relays Testing
RECLOSING AND SYNCH-CHECK RELATED LEDS
(
OPTIONAL
)
RECLOSING IN SERVICE
Yellow
ON – dc power ON
LOCKOUT
Yellow
Reclosing Logic in Lockout State
FAILED RECLOSE
Yellow
Breaker associated with Recloser failed to reclose
HBDL
Yellow
Bus is Live and Line is Dead
HLDB
Yellow
Line is Live and Bus is Dead
SYNCHRONISM
Yellow
Bus and Line Voltages in Synchronism
FRONT PANEL LED INDICATOR CHART
4. 4.
FRONT PANEL MAN-MACHINE INTERFACE
4.4.1
LED Indicators
The REL 301/302 comes with LEDs on the front panel. “IN SERVICE” LED should be
on, all other indicators are off in normal conditions, but after a trip, the ones related
to the trip blink. If a second trip occurs, the LEDs related to the latest fault double
blink. See Section 5.1.1 for more details.
4.4.1.1
LEDs and Display Reset
The push-button labelled RESET is used to reset all the trip LEDs and send the display
to the metering mode.
4.4.2
Display Module
The front panel operation provides a convenient means of checking and changing set-
tings, and for checking relay unit operations after a fault.
It consists of a 2-line 16-character/line LCD display, 4 push-buttons (SELECT, LOW-
ER, RAISE, ENTER) and a switch. The latter selects the display of either the protection
or the optional recloser. It should always be in protection mode when no reclosing in-
formation is being viewed or during re-initialization.
The front panel has different modes of operation, shown at the top right of the display.
The 4 push-buttons labeled SELECT, LOWER, RAISE, and ENTER, are used to inter-
face with the REL 301/302 relay menu and settings.
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...