I.L. 40-386.3
(10/94)
3-3
• Zero sequence impedance: /
Z
0L
(pri) = 50
∠
73
°
ohms
• Current Transformer Ratio (
CTR
):
RC = 1200/5 = 240
(Set CTR = 240)
• Voltage Transformer Ratio (
VTR
):
RV = 600/1 = 600(Set VTR = 600)
Relay secondary ohmic impedances are:
Z
= Z
pri
x R
C
/R
V
Z
1L
= Z
2L
= 15
∠
77
°
x 240/600 = 6
∠
77
°
ohms
Z
0L
= 50
∠
73
°
x 240/600 = 20
∠
73
°
ohms
3.2.1
Ratio of Zero and Positive Sequence Impedances (ZR)
ZR = Z
0L
/Z
1L
= 20/6 = 3.33
Then REL 301/302 will automatically calculate the zero sequence current compensa-
tion factor (k
0
) by using the value of Z
OL
/Z
IL
, i.e.,
NOTE:
The setting range of ZOL/ZIL has been expanded 0.1 - 7.0 to 0.1 - 10.
Also the setting ranges of Ang Pos. (Positive sequence line impedance
angle) and Ang Zero (Zero sequence line impedance angle) have been ex-
panded from 40
°
-90
°
to 10
°
-90
°
as well. These changes were made to
accommodate a wide variety of system components and configurations.
However, the selection of each setting has to be carefully considered if
the maximum fault current is 200 Amperes (secondary or above).
If the maximum fault current is 200 Amperes (secondary) the following
restrictions must be observed:
ZOL/ZIL less than or equal to 7.5
The setting difference of |Ang Pos| - |Ang Zero| = 50 or less
If the maximum fault current is less than 200 Amperes (secondary)
these restrictions do not apply.
3.2.2
Zone1 Distance Settings
A setting of 80% of the line impedance for Zone1 reach is recommended, thus the
Zone1 phase and ground reach should be
Zone1 Ø = 6 x 0.8 = 4.8 and
Zone1 G = 6 x 0.8 = 4.8
NOTE:
Zone1 Ø and Zone1 G can be set for different values if the applica-
tion is required.
As stated above, start with a setting of 80% of the line impedance for the Zone1 reach
setting. Adjustment of the Zone1 reach (line percentage) should be considered if any
of the following are true:
k
0
=
Z
0
L
Z
1
L
–
(
)
/3
Z
1
L
=
ZR
GANG
PANG
–
1
–
(
)
∠
[
]
/3
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...