I.L. 40-386.3
3-12
(10/94)
3.3.23 Polarizing Settings
Settings for the directional ground overcurrent polarization is controlled by the setting
of
Dir Type
. It has 3 selections:
Zero Sequence
—Zero sequence voltage polarization.
Negative Sequ
—Negative sequence voltage polarization.
Dual Polariz
—Both zero sequence voltage and current polarization.
3.3.24 Overcurrent Ground Backup
The overcurrent ground backup function provides seven sets of curves, which are
similar to the CO curves, for backing up the ground distance protection. Four set-
tings
(GB Type, GB Pickup, GBT Curve
and
GB Dir)
must be determined for applying
this function.
a.
GB Type is the ground backup curve selection. Seven sets of familiar CO curves are pro-
vided (C02,5,6,7,8,9 and 11), and are
shown in Figures 2-32 thru 2 -38. The selection is
based on the application and coordination time. A selection of Disabled prevents the
ground backup function from operating.
b.
GB Pickup is the current level setting. The setting range is 0.5 to 4.0 amperes in 0.5 steps.
In general, the current level setting criteria is:
(I
Fmin
/2) >
GB Pickup
> 2 x Max. Residual 3I
0
where I
Fmin
= Minimum ground fault current for a fault two buses away
For the best sensitivity,
GB Pickup
should be set at 0.5 amperes, this is normally
adequate for most applications.
c.
GBT Curve is the time delay setting of the ground backup function.
As shown in Figures
2-32 thru 2 -38, the GBT Curve is settable in steps of one from 1 to 63. As with any time
delay overcurrent function, the time delay setting must be coordinated with other overcur-
rent devices.
d.
GB Dir is the setting for directional control selection. The ground backup function becomes
a forward-directional torque control overcurrent ground function if GB Dir is set to YES. If
GB Dir is set to No, the overcurrent ground backup function is non-directional and will pro-
duce a trip output for faults in the forward and reverse direction.
The following equation can be used to calculate the trip time for all CO curves from CO-2 thru
CO-11 :
T (sec) =
(for 3I
0 ≥
1.5)
T (sec) =
(for 1<3I
0
< 1.5)
Where 3I
0
=
GB Pickup
= Pickup setting
T
0
K
3
I
0
C
–
(
)
P
--------------------------
+
GBT Curve
24 000
,
--------------------------------
×
R
3
I
0
1
–
(
)
---------------------
GBT Curve
24 000
,
--------------------------------
×
I
F
GB Pickup
-------------------------------
Summary of Contents for REL 301
Page 1: ......
Page 8: ......
Page 17: ...I L 40 386 3 1 10 10 94 2682F39 Sheet 1 of 2 Sub 2 Figure 1 2 REL 301 302 Layout Vertical...
Page 18: ...I L 40 386 3 10 94 1 11 2682F39 Sheet 2 of 2 Sub 2 Figure 1 3 REL 301 302 Layout Horizontal...
Page 19: ......
Page 20: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 49: ......
Page 51: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 60: ......
Page 62: ...I L 40 386 3 10 94 2 41 Figure 2 32 CO 2 Curve Characteristics 619596 Sub 2...
Page 63: ...I L 40 386 3 2 42 10 94 Figure 2 33 CO 5 Curve Characteristic 619597 Sub 2...
Page 64: ...I L 40 386 3 10 94 2 43 Figure 2 34 CO 6 Curve Characteristic 619598 Sub 2...
Page 65: ...I L 40 386 3 2 44 10 94 Figure 2 35 CO 7 Curve Characteristic 619599 Sub 2...
Page 66: ...I L 40 386 3 10 94 2 45 Figure 2 36 CO 8 Curve Characteristic 619600 Sub 2...
Page 67: ...I L 40 386 3 2 46 10 94 Figure 2 37 CO 9 Curve Characteristic 619601 Sub 2...
Page 68: ...I L 40 386 3 10 94 2 47 Figure 2 38 CO 11 Curve Characteristic 619602 Sub 2...