I.L. 40-385.1B
(5/92)
5-1
Section 5. SETTING CALCULATIONS
5.1.3
Zone 2 Distance Unit Settings
Generally, Zone-2 reach is set for 100% of the pro-
tected line plus 50% of the shortest adjacent line. If
the shortest (or only) adjacent line primary imped-
ance is 20 ohms, then the Zone-2 reach setting
would be:
Z2P = 6 + (20 x 0.5) x 240/600 = 10 and
Z2G = 10
NOTE:
Z2P and Z2G can be set for different
values if the application is required.
5.1.4
Zone 3 Distance Unit Settings
Generally, Zone-3 reach is set for 100% of the pro-
tected line plus 100% of the longest adjacent line
emanating from the remote bus, while accounting for
the infeed from the same remote bus.
If the longest (or only) adjacent line from the remote
bus is 25 ohms primary, and the infeed effect may in-
crease its impedance by 30%, then the Zone-3
reach setting should be:
Z3P = 6 + (25 x 1.3) x 240/600 = 19 and
Z3G = 19
NOTE:
Z3P and Z3G can be set for different val-
ues if the application is required.
5.1.5
Overcurrent Unit Setting
a. The low set phase overcurrent unit is used for su-
pervising the OSB, the load-loss-trip and CIF func-
tions. It should be set higher than the line charging
current and below the minimum load current.
NOTE:
It should be set above the maximum
tapped load current if applicable.
Assume that the line charging current is negligible
for this line section, and the minimum load current is
2.0 A secondary, then the low set phase overcurrent
unit setting should be:
IL = 1
b. The low-set ground overcurrent unit is used for
supervising the reverse directional overcurrent
ground unit (RDOG). It should be set as sensitive as
possible. A setting of 0.5 amperes is recommended:
IOS = 0.5
Z
1L
= Z
2L
= 15
∠
77
°
x 240/600 = 6
∠
77
°
ohms
Z
0L
= 50
∠
73
°
x 240/600 = 20
∠
73
°
ohms
5.1.1
Ratio of Zero and Positive Sequence
Impedances
ZR = Z
0L
/Z
1L
= 20/6 = 3.33
then MDAR will automatically calculate the zero se-
quence current compensation factor (k
0
) by using
the value of ZR, i.e.,
5.1.2
Zone 1 Distance Unit Settings
A setting of 80% of the line impedance for zone-1
reach is recommended, thus the Zone-1 phase and
ground reach should be:
Z1P = 6 x 0.8 = 4.8 and
Z1G = 6 x 0.8 = 4.8
NOTE:
Z1P and Z1G can be set for different val-
ues if the application is required. Refer
to Section H, Step 10 for calculation and
example.
k
0
Z
oL
Z
1
L
–
(
)
/3
Z
1
L
ZR
GANG
PANG
–
(
)
-1
∠
[
]
/3
=
=
5.1
CALCULATION OF MDAR SETTINGS
The following MDAR setting calculations correspond
to the setting categories in the Installation Section
(4). Assume that the protected line has the following
data:
• 18.27 miles
• Line reactance 0.8 ohms/mile
• 69 kV, 60 cycles
• Positive and negative sequence impedances:
ZIL(Pri) = Z2L(Pri) = 15
∠
77
°
ohms
• Zero sequence impedance: /
Z
0L
(pri) = 50
∠
73
°
ohms
• Current Transformer Ratio (CTR):
RC = 1200/5 = 240
(Set CTR = 240)
• Voltage Transformer Ratio (VTR):
RV = 600/1 = 600
(Set VTR = 600)
• Relay secondary ohmic impedances are:
Z = Z
pri
x R
C
/R
V
Summary of Contents for REL-300
Page 30: ......
Page 32: ......
Page 33: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ...I L 40 385 1B SD 6 5 92 Figure SD 2 MDAR Block Diagram sheet 1 of 1 Sub 1 1611C12...