INTERCONNECT Module
JMP 1 to 6, & 13
For the rated input dc voltage
JMP 7 & 9
For Stub Bus Protection
JMP 8 & 10
For the trip alarm (AL2-2)
JMP 11 & 12
For MDAR with FT switches only
MICROPROCESSOR Module
JUMPER
POSITION
FUNCTION
JMP 1
1-2
EEPROM (8kx8)
JMP 2
2-3
Standard
JMP 3
IN
Spare jumper
JMP 4
OUT
No dropout time delay for trip contacts
JMP 5
OUT
Disable output contact test
JMP 6
OUT
Normal operation
JMP 8 & 9
1-2
RAM (32kx8)
JMP 10
IN
Spare jumper
JMP 11 & 12
OUT
Spare positions
TABLE 4-4. RECOMMENDED JUMPER POSITIONS (V2.XX)