![ABB REL-300 Instruction Leaflet Download Page 59](http://html1.mh-extra.com/html/abb/rel-300/rel-300_instruction-leaflet_3472904059.webp)
I.L. 40-385.1B
3-14
(5/92)
pole-A, pole B and C close at a later time (refer to
Figure 3-28). If, due to breaker contact asymmetry,
the first breaker contact to close is the one of the
faulted-phase, the zero-sequence (or negative se-
quence) polarizing voltage will initially have a polari-
ty opposite to its fault-derived polarity, the reverse-
looking ground unit could pick-up for a short period,
issue a blocking order, and maintain it for 50 ms con-
sequently, the correct tripping will be delayed. The
Block-the-Block logic would prevent this delaying.
The Reverse-Block logic also includes the reverse
looking Z3P/Z3G units as shown in Figure 3-32.
3.7
3-ZONE DISTANCE PHASE AND GROUND
WITH INDEPENDENT PILOT PHASE AND
GROUND
There are four impedance units per zone: one
phase-to-phase unit and three phase-to-ground
units (see also Section 3.3). The following table
shows the role of each distance unit per pilot zone
scheme.
Distance Units
Scheme
Z1P/Z1G
Z3P/Z3G
PLTP/PLTG
(Reverse)
POTT/
UNBLOCK
----
Key/Trip
PUTT
Start Key
----
Trip
BLOCK
----
Start Key
Trip and Stop Key
NOTE: Beyond pilot logic functions, Z1P/Z1G
and Z3P/Z3G perform basic Zone 1 and
Zone 3 functions.
3.8
INVERSE TIME DIRECTIONAL OR NON-DI-
RECTIONAL (SELECTABLE)
OVERCURRENT GROUND BACKUP.
(See Section 3.4.2)
3.9
INSTANTANEOUS FORWARD DIRECTION-
AL OVERCURRENT FUNCTION FOR HIGH
RESISTANCE GROUND FAULT SUPPLE-
MENT TO OVERREACH PILOT.
Supplemental protection is provided on overreach-
ing pilot systems to detect high resistance ground
faults. The instantaneous forward directional over-
current ground function (FDOG) works in conjunc-
tion with the pilot ground distance unit. The FDOG
directional unit is determined by the setting of DIRU
(ZSEQ/NSEQ/DUAL). Refer to Section 3.4.11 for
the setting of DIRU. FDOG is supervised by the Iom
setting. A coordination timer FDGT (T/0) is provided
to allow preference for pilot ground distance (mho)
unit operation. The delay time (T) can be set from 0
to 15 cycles in 1 cycle steps. It is recommended to
set the FDGT timer to 3 cycles or longer for security
reasons.
3.10 INSTANTANEOUS REVERSE DIRECTION-
AL OVERCURRENT GROUND FUNCTION.
Similar to FDOG, the instantaneous reverse direc-
tional overcurrent ground function (RDOG) supple-
ments the pilot zone logic.
3.10.1 Supplement to Reverse Z3G Trip.
In the blocking system, RDOG, supervised by IOS,
provides additional ground fault detection (high re-
sistance) beyond what is available by Z3G (reverse
looking) for carrier start.
3.10.2 Carrier Ground Start on Blocking Scheme
In the POTT/UNBLOCK systems, RDOG supervises
PLTG and prevents keying or tripping on reverse
faults.
3.10.3 Weakfeed System Application
For weakfeed applications, an inherent part of the
logic requires reverse fault detection; Z3P/Z3G and
RDOG supply this requirement.
3.11 LOSS-OF-POTENTIAL SUPERVISION
(LOP, See Section 3.4.3)
3.12 LOSS-OF-CURRENT MONITORING (LOI,
See Section 3.4.4)
3.13 OVERCURRENT SUPERVISION (See Sec-
tion 3.4.5)
3.14 INSTANTANEOUS OVERCURRENT TRIP
(See Section 3.4.6)
3.15 HIGH-SET INSTANTANEOUS DIRECT
TRIP, INCLUDING THREE-PHASE AND
ONE GROUND OVERCURRENT UNITS
FOR SPT/3PT APPLICATION (See Section
3.4.6)
3.16 CLOSE-INTO-FAULT TRIP AND STUB BUS
PROTECTION (See Section 3.4.7)
Summary of Contents for REL-300
Page 30: ......
Page 32: ......
Page 33: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ...I L 40 385 1B SD 6 5 92 Figure SD 2 MDAR Block Diagram sheet 1 of 1 Sub 1 1611C12...