
I.L. 40-385.1B
(5/92)
6-5
voltages are necessary as directional
reference. The ITG and ITP will automat-
ically become non-directional over-
current units if the setting of LOPB is
YES and at least one input voltage is
zero volts (e.g., LOPB = YES in the me-
tering mode).
Step 21. Using Figure 6-1, configuration #1, to con-
nect currents and voltages, apply AG fault as
shown in Step 1.1.3. The MDAR should trip at I
a
= 5 Amps
±
5 % with a target of ITG-AG. For re-
versed fault, apply 10A reversed fault current
(i.e., I
a
leads Van by 135
°
for Y-connection, or
105
°
for T-connection). The relay should not trip.
Step 22. Using Figure 6-3, to connect currents and
voltages, apply AB fault as shown in Step 1.1.5.
The MDAR should trip at Iab = 10 Amps
±
5%,
with a target of ITP - AB. Apply a 15A reversed
fault current (i.e., I
a
leads V
ab
by 135
°
for Y-con-
nection or 105
°
for T-connection). The relay
should not trip.
1.1.9
Ground Backup (GB) Test
Step 23. Use the SETTINGS mode and change the
following settings:
• ITP
= “OUT”
• ITG
= “OUT”
• GBCV
= CO-8
• GBPU
= .5
• GDIR
= “NO”
• GTC
= 24
NOTE: The note in Step 20 applies to the GB
test. The GB can be set to directional
ground overcurrent. For loss-of-poten-
tial condition, GB will be converted to
non-directional, automatically, regard-
less of the GDIR=YES setting.
Using Figure 6-1, apply A-G fault of 4.1A to MDAR.
Trip time is determined as follows:
(T
MSEC
) =
where
(3I
OF
is zero sequence fault current.)
478
4122
3I
0
1.27
–
-------------------------
+
GTC
24
------------
3I
0
3I
OF
GBPU
-----------------
=
The single-phase trip currents for Zone 1, Zone 2,
and Zone 3 at the maximum torque angle
are 6.0A, 4.5A and 3.0A, respectively.
b. Phase-to-Phase Fault
Use the T-connection and the equation in step 13.
Apply the following input voltages:
The single-phase trip currents for Zone 1, Zone 2
and Zone 3 at the maximum torque angle
are 4A, 3A and 2A, respectively.
c. Three-Phase Fault
Use the equation in Step 12 with the following input
voltages:
The three-phase trip currents for Zone 1, Zone 2 and
Zone 3 at the maximum torque angles
should be 6.0A, 4.5A and 3.0A, respectively.
1.1.8
Instantaneous Overcurrent (High-Set
Trip)
Step 20. Using the SETTINGS mode, change the
following settings:
ITP = 10A
LOPB
= “NO”
ITG = 5A
Z3G
= “OUT”
Z3P
= “OUT”
NOTE: The High-Set ground overcurrent (ITG)
and phase overcurrent (ITP) are super-
vised by Forward Directional Ground
unit (FDOG) and Forward Directional
Phase unit (FDOP), respectively. In or-
der to test the High-Set trip, the 3
φ
I
A
75
°
∠
(
)
V
AN
18 0
°
∠
1
2
---
V
F
=
=
V
BN
18
180
°
–
∠
1
2
---
V
F
=
=
V
CN
105 90
°
∠
=
I
AB
75
°
–
∠
(
)
V
AN
27 0
°
∠
V
LN
=
=
V
BN
27
120
°
–
∠
=
V
CN
27 120
°
∠
=
I
A
75
°
, I
B
195
°
, I
C
+45
°
∠
–
∠
–
∠
(
)
Summary of Contents for REL-300
Page 30: ......
Page 32: ......
Page 33: ......
Page 38: ......
Page 39: ......
Page 40: ......
Page 41: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 45: ......
Page 62: ......
Page 63: ......
Page 64: ......
Page 65: ......
Page 66: ......
Page 67: ......
Page 68: ......
Page 69: ......
Page 70: ......
Page 71: ......
Page 72: ......
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ......
Page 77: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ...I L 40 385 1B SD 6 5 92 Figure SD 2 MDAR Block Diagram sheet 1 of 1 Sub 1 1611C12...