8 . . .Diagnosis / error messages
. . .Overview
Error no . / Range
Error text
Current output
Digital output
Pulse output
LCD display
Error maskable?
C078.004 / Config.
Flowrate to zero.
Check digital in
terminals.
4 mA (0 % flow)
Current value - no
change.
0 Hz
0 %
Menu "...Group
Masking".
C076.006 / Config.
All totalizer stopp.
Check digital in
terminals.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value -
no change.
C074.007 / Config.
Totalizer reset.
Reset of one or more
Totalizers.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value -
no change.
Menu "...Group
Masking".
C072.003 / Config.
Simulation is on
Simulated values.
Switch off Simulation
Mode.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value -
no change.
C070.027 / Config.
An alarm is
simulated.
Switch off alarm
simulation.
Current value - no
change.
Current value - no
change.
Current value - no
change.
Current value -
no change.
S065.044 / Operation
Inhouse temp. alarm.
Reduce ambient
temperature.
Current value - no
change.
No response
No response
Current value -
no change.
S064.041 / Operation
EPD alarm.
Secure pipe is
completely filled.
Alarm - as configured in
menu "Curr. at EPD
Alarm".
Alarm if DO is
configured as "Logic /
Alarm Signal / EPD".
0
0 %
Menu "...Group
Masking".
S062.039 / Operation
Sensor temp. limits
alarm. Change limits
or change fluid
temperature.
Current value - no
change.
No response
Current value - no
change.
Current value -
no change.
Menu "...Group
Masking".
S052.017 / Operation
Curr.Out 31 / 32 is
saturated. CO
process value out of
range. Adapt Qmax.
Alarm - as configured in
menu "Curr.Out >
20.5mA".
Current value - no
change.
Current value - no
change.
Current value -
no change.
Menu "...Group
Masking".
S047.016 / Operation
Pulse output is cut
off. Wrong config.
Check pulse out
configuration.
Current value - no
change.
Current value - no
change.
Maximum possible
pulse rate
Current value -
no change.
Menu "...Group
Masking".
S046.001 / Operation
Mass flowrate
exceeds limits. Check
flowrate and alarm
limits.
Current value - no
change.
Alarm if DO is
configured as "Qm
Massflow Max" or "Qm
Massflow Min".
Current value - no
change.
Current value -
no change.
Menu "...Group
Masking".
S044.002 / Operation
Volume flowrate
exceeds limits. Check
flowrate and alarm
limits.
Current value - no
change.
Alarm if DO is
configured as "Qv
Volumeflow Max" or "Qv
Volumeflow Min".
Current value - no
change.
Current value -
no change.
Menu "...Group
Masking".
S041.034 /
Electronics
DC feedback
regulation. Check
conditions of
application. Call
service.
4 mA (0 % flow)
No response.
0 Hz
0 %
Menu "...Group
Masking".
S040.031 /
Electronics
Coil impedance
alarm. Call service.
Current value - no
change.
No response.
Current value - no
change.
Current value -
no change.
Menu "...Group
Masking".