FEM610 |
PROCESSMASTER | OI/FEM610-EN REV. A
8 . . .Diagnosis / error messages
. . .Error messages
Operation outside of specifications (Out Of Spec .)
Error no . / Range
Text on the LCD display
Cause
Remedy
S065.044 / Operation
Inhouse temp. alarm. Reduce
ambient temperature.
Fluid or ambient temperature is out of spec.
Check proces conditions reduce temperature.
S064.041 / Operation
EPD alarm. Secure pipe is
completely filled.
Sensor not filled.
Check for empty pipe Make sure sensor is
filled completely.
S062.039 / Operation
Sensor temp. limits alarm.
Change limits or change fluid
temperature.
The fluid temperature is out of Limits.
Check process condition and adjust alarm
limits.
S052.017 / Operation
Curr.Out 31 / 32 is saturated. CO
process value out of range. Adapt
Qmax.
The selected current output 31 / 32 process
value is out of measuring range.
Adapt measuring range.
S047.016 / Operation
Pulse output is cut off. Wrong
config. Check pulse out
configuration.
The caluclated output pulse or frequency is
above the configurated limit frequency.
Check pulse out configuration.
S046.001 / Operation
Mass flowrate exceeds limits.
Check flowrate and alarm limits.
The mass flow is below or above the
configured limit values "Qm Massflow Min"
and "Qm Massflow Max".
Check the parameter settings in the "Process
Alarm / ...Alarm Limits" menu and adjust if
necessary. Check mass flow.
S044.002 / Operation
Volume flowrate exceeds limits.
Check flowrate and alarm limits.
The volume flow is below or above the
configured limit values "Qv Volumeflow Min"
and "Qv Volumeflow Max".
Check the parameter settings in the "Process
Alarm / ...Alarm Limits" menu and adjust if
necessary. Check volume flow rate.
S041.034 / Electronics
DC feedback regulation. Check
conditions of application. Call
service.
Multi-phase measuring media that produce a
very high level of noise. Stones or solids that
produce a very high level of noise.
Galvanic voltages at the measuring
electrodes.
Conductivity of measuring medium is not
evenly distributed (e.g., directly after
injection points).
Contact ABB Service.
S040.031 / Electronics
Coil impedance alarm. Call
service.
Coil Inductance changed, coil damaged, coil
isolation damaged, outer magnetic fields.
Contact ABB Service.
Error no . / Range
Text on the LCD display
Cause
Remedy
M038.010 / Electronics
Sensor memory defective.
Mem. or connect. defective.
Replace memory.
Defective NV-Memory module. NV-Memory
module is not plugged in.
Check if NV-Memory module is plugged in.
Call Service.
M037.015 / Electronics
NV chips defect on Motherboard.
Defective MB. Replace MB. Call
Service.
Defective NV-Memory.
Exchange Motherboard. Call Service.
M032.023 / Config.
Curr.Out 31 / 32 not calibrated.
Call Service.
The Current Output 31 / 32 is not calibrated.
Call Service.
M028.008 / Config.
Display value is < 1600 h at
Qmax.
Change mass Unit or vol. Unit for
Totalizer.
Totalizer unit is too small.
Change the mass or volume totalizer unit.
M026.005 / Config.
Maintenance interval is reached.
Perform maintenance.
Set "Preset Maint. cycle" to zero to deactivate
the maintenance timer.
Perform maintenance work. Start new cycle.
M024.009 / Config.
Device not calibrated.
Call Service.
The device is not calibrated.
Call Service.
Maintenance