FEM610 |
PROCESSMASTER | OI/FEM610-EN REV. A
6 . . .Commissioning
Factory settings
The device can be factory parameterized to customer
specifications upon request. If no customer information is
available, the device is delivered with factory settings.
Switching on the power supply
• Switch on the power supply.
The LCD display shows the following display during the
startup process:
The process display is displayed after the startup process.
Parameterization via the "Easy Setup"
menu function
Settings for the most common parameters are summarized in
the ‘Easy Setup’ menu. This menu provides the fastest way to
configure the device.
The following section describes parameterization via the
‘Easy Setup’ menu function.
1
Switch to the configuration level with
.
2
Use
/
to select ‘Standard’.
3
Confirm the selection with
.
4
Use
to confirm the password. A password is not
available as factory default; you can continue without
entering a password.
Parameter
Factory setting
Qv Max 1
Q
max
DN (see table in chapter "Measuring
range table" on page 34)
Sensor Tag
None
TX Location TAG
None
Unit Volumeflow Qv
ugal/min (US galon/minute)
Unit Vol. Totalizer
ugal (US galon)
Pulses per Unit
1
Pulse Width
100 ms
Damping
1 s
Digital output 41 / 42
Impulse für Forward & Reverse
Digital output 51 / 52
Flow Direction
Current output
4-20mA FWD/REV
Curr.Out at Alarm
High Alarm, 21.8 mA
Current at flowrate > 20.5 mA
Off
Low Flow Cut Off
1 %
EPD Alarm
Off
Enter Password
**********
RSTUVWXYZ012345
Next
OK
Access Level
Read Only
Back
Select
Standard
System Startup
Processing
Q
∑+
∑-
0.00
0000.00
0000.00
ugal/s
ft³
ft³
Process Display