FEM610 |
PROCESSMASTER | OI/FEM610-EN REV. A
Menu / parameter
Description
Input/Output / ...Dig.Out 41/42 / ...Setup Logic Output
Logic Output Action
Selection of binary output function.
• Off: The binary output is deactivated.
• F/R Signal: The binary output indicates the flow direction.
• Alarm Signal: The binary output indicates an active alarm. The alarm is selected in the "...Alarm Config"
menu.
• Dual Range: The binary output is activated when measuring range 2 (Qm Max 2 / Qv Max 2) is selected.
This selection is only available if the parameter "Dual Range" has been configured to Qm or Qv.
Active Mode
Select switching properties for the binary output.
• Active High: Normally open
• Active Low: Normally closed
Default setting: Active High.
7 . . .Operation
. . .Parameter descriptions
Input/Output / ...Dig.Out 41/42 / ...Alarm Config
General Alarm
Select error messages signaled via the binary output 41 / 42.
Only if the parameter "Logic Output Action" is set to Alarm Signal.
Default setting: Off.
Qv Volumeflow Max
Qv Volumeflow Min
EPD
Input/Output / ...Dig.Out 51/52
Mode
Selection of the operating mode for digital output 51 / 52. The "Follow DO 41 / 42, 90° Shift, 180° Shift"
operating modes are only available if digital output 51 / 52 has been configured as a pulse output.
• Off: Digital output deactivated.
• Logic: Digital output functions as binary output (for function see parameter "„...Setup Logic Output").
• Follow DO 41 / 42: Digital output 51 / 52 operates according to the pulses from digital output 41 / 42. The
function depends on the setting for the parameter "Outp. Flow Direction".
•
90° Shift: 90° phase-shifted output of the same pulses as for digital output 41 / 42.
•
180° Shift: 180° phase-shifted output of the same pulses as for digital output 41 / 42.
Default setting: Logic.
Outp. Flow Direction
Selection of flow direction in which the pulse / frequency output issues the selected process value.
The parameter is only available if Follow DO 41 / 42 has been configured for digital output 51 / 52 in
parameter "Mode".
• No pulses are issued if "Forward & Reverse" is selected. Only digital output 41 / 42 is active.
• When "Forward" is selected, pulses for forward flow are issued at digital output 41 / 42 and pulses for re-
verse flow at digital output 51 / 52.
• When "Reverse" is selected, pulses for reverse flow are issued at digital output 41 / 42 and pulses for for-
ward flow at digital output 51 / 52.
. . .Setup Logic Output
Selection of submenu ‘...
Setup Logic Output’
using .
Only available if ‘ModeLogic’ has been selected.
. . .Alarm Config
Selection of submenu ‘...
Alarm Config’
using .
Only available if ‘ModeLogic’ has been selected.
. . .Menu: Input/output