L840/MG4
78
Exit the Hardware menu with button
X
and assign the circuit module to
the areas.
As standard all circuit modules are assigned to area 1.
Test the individual circuits.
Note:
After logging off a circuit module, the freed circuits are replaced by the
following circuit, i.e. all the following circuits are moved upwards.
For this
reason all circuits (properties, type, area and text) must be inspected from
the logged off circuit module and must be checked and corrected if
necessary.
After teach-in the Detector Circuit Module L840/MG4 has four circuits each
with the following properties:
(also refer to
Properties of the circuit types
chapter 8.1.3.2 on page 56)
Standard
or
EIB/KNX
Intrusion circuit (Cct)
Cct off int off
Cct off ext. off
Silent alarm off
Print unset off
The circuits are thus active with internal and external setting.
After pressing
button
5
“? Cct Fault” on the keypad, the faults of the individual circuit are
displayed (e.g. Cct14 or the stored text for the detector).
The circuits can also be reprogrammed to other circuit types (e.g. personal
attack or technology circuits).
Area assignment
On the programming level (Engineer menu) select function “07=Concs”.
Concentrator
Number _
Enter the address of the circuit.
Concentrator-0x
Area-1
Enter the circuit area and exit the Hardware menu with button
X
.
Remove jumper LK1 after commissioning, insert the spring for the panel
tamper contact and close the enclosure cover.