Configuration and Programming by the Engineer
58
Prevent Set
Circuit -0xx
Prevent Set-On
0=Off;
1=On
Technical circuits can cause a prevention of setting on a fault.
Off:
An interrupted circuit does not prevent setting.
On:
An interrupted circuit prevents setting.
8.1.4 Menu 04 “Relay”
Menu item “04=Relay”:
Both relays on the main PCB are already pre-
programmed in the factory:
Relay 1 (terminals 19, 20, 21): External set (area 1).
Relay 2 (terminals 22, 23, 24): Walk test.
Both relays are assigned to area 1 and can be reprogrammed to the
following functions:
Display
Description
01=Intruder
Active on an intrusion alarm for the set alarm time
02=PA
Active on a personal attack alarm for the set alarm
time
03=Ext Set
Active with externally set area 1
04=Fault
Active with a mains/battery fault (delayed up to 15
minutes) and processor failure
05=Set Confirm
Active for about 3 seconds after ext. setting of area 1
06=Ready to Set
Active if area 1 ready to set
07= Internal Alarm
Active with internal alarm in area 1
08=Walk Test
Active with switched on walk test
09=Tamper
Active with tampering alarm
10=Int Set
Active with internally set area 1
11=Reset
Active on a reset for about 5 seconds
12=Int/Ext Set
Active with internally or externally set area 1
13=KNX-Fault
Active with KNX error
14=Fire-Alarm
Active when a fire circuit is triggered
Programming of a relay:
Relay
Number _
(Limit 1 or 2)
Relay-1
Ext Set
(Button
?
for number/selection of function)
Engineer-PIN
01 = System Size
02 = Area Opts
03 = Circuits
04 = Relay
05 = Alarm Times
06 = Keypads
07 = Concs *
08 = User Auth
09 = Text
10 = L240/B/BS*
11 = XS/1.1 KNX *
13 = 2-Conc Tamper *
15 = Defaults
16 = XIB-Detectors
8 = Edit