Operation by the Engineer
42
Submenu
“04=SiteID”
In
submenu “04=SiteID”
a 4-digit customer number must be entered for the
panel. This customer number in the panel must be identical with the
customer number in the database of the PC Software (WIN-PC). When
communication is established both customer numbers are compared, and
communication will only be possible if they are identical.
SiteID
0
Enter the customer number
Further submenus only appear after the Ethernet connection type is
selected.
Submenu
“05=Panel-IP”
In
Submenu “05=Panel-IP”
the IP address of the network module L240/IP
is entered. The point between the numbers can be achieved by pressing the
arrow key “ ”.
Panel-IP
192.163.3.3
Entry of the L240/IP IP address
The Interface Module L240/IP requires a fixed IP address setting for
operation. The network section of the address (defined by the subnet mask)
must comply over the entire network. The device section of the address
(generally the last number block) is used for addressing the individual
devices. The IP address used here is only an example and can vary
according to the network.
Generally, the properties of the Internet protocol for the PC settings are set
to “Obtain an IP address automatically”. This setting must be checked and a
fixed IP address setting may need to be set.
The following example shows how the IP address of a PC is changed
(Example: Windows XP).
Note: The settings must be made by a person with appropriate experience in
the configuration of PCs and network technology. Consult your system
administrator if required.
Access the network settings:
Start – Control Panel - Network and Internet Connections
Double click on the respective network connection under
LAN or High-
Speed Internet
and click on
Properties
.
The
window
Properties of LAN Connection
opens.
Select
Internet Protocol (TCP/IP)
from the list and click on
Properties
.
Activate “Use the following IP address” and enter the new IP address (in
our example the IP address 192.168.3.1) and Subnet Mask.
IMPORTANT: Note the old IP setting so that you can reactivate it!
Submenu
“06=Panel Port
”
In
submenu “06=Panel Port”
the port number used by WIN-PC can be
found. This is fixed and should not be changed.
Panel Port
6000