Configuration and Programming by the Engineer
49
The apartment (area 2/main area) can only be set if the office (area 1/sub-
area) has been set. This ensures that setting of the office area cannot be
forgotten when leaving the building. On returning home the apartment must
be unset and only then can the office be unset.
Deleting the dependencies of the areas is undertaken in the respective area
menus (enter with button “0” or Off).
Assignment of area-relevant messages
If different areas have been introduced, there is often a demand to
differentiate between messages and signals from the individual areas and to
transfer them to a control centre. In the following sub-menus, different
messages (e.g. external setting area 2) to one of the transistor outputs 11-18
can be programmed for this purpose. Accordingly, one channel of a
transmission device can be used. The outputs can also be used for other
control functions.
For each area the following signals are available:
External
alarm
Internal
alarm
External
set
Reset
(pulse)
Personal
attack
Fault
Setting (arming) acknowledgement
Ready to set
Internal
alarm
Unset
Fire
alarm
Example:
The internal alarm for area 2 should be programmed to transistor output 7.
In menu item “02=Area Opts” area 2 and the sub-menu “10=Int Alm TX“
should be selected:
Area
Number 2
Press button 2
10=Int Alm TX
11=Unset TX
Press buttons 1 0
Area-2 Int Alm
TX-7
Select output 7
Area-2 Int Alm
Device-0
Press button 0 (central outputs)
Area-2 Int Alm
Invert-Off
Press button 0 for
Off
(Invert Off)
Now when there is an internal alarm from area 2, transistor 7 (terminal 17)
will switch.